background image

Chapter 1:  Getting Started

Page 1–5

S

tride

®

 MB Gateway User Manual

 – 

1st Edition Rev. E – August 2020

Hardware Reset Button

The Hardware Reset Button is a small 

recessed button located on the top of the 

device. Pressing the button will reset all 

settings to their default values.

DIP Switches

A 120Ω termination resistor for each serial 

port is enabled (ON) or disabled (OFF) by the 

corresponding DIP switch.

LEDs

The front panel provides status via the 

following LEDs:

PWR1 (Green)

LED ON indicates voltage is applied to 

Power 1 terminals.

PWR2 (Green)

LED ON indicates voltage is applied to 

Power 2 terminals.

RUN (Green)

Blinking Indicates the device is functioning 

normally. Steady on indicates power is on 

and device is booting up.

SPEED (RJ45 Yellow)

There is one yellow SPEED LED for each 

Ethernet port. LED ON indicates Ethernet 

speed is 100 Mbps. LED OFF indicates 

Ethernet speed is 10 Mbps. 

Link/Activity (RJ45 Green)

There is one green 

L

ink

/A

ctivity

 LED for each 

Ethernet port. The 

L

ink

/A

ctivity

 LED is ON 

when a valid link is established, and flashes 

to indicate that the gateway sees data traveling on the Ethernet network. If any network device 

is sending or receiving data, the 

L

ink

/A

ctivity

 LED will be flashing. During heavy communication 

loads, this indicator will be steady ON. If the LED is OFF, then a problem with the Ethernet 

connection has been detected.

T (Serial port Transmit, Green) 

The T or 

t

rAnsmit

 D

AtA

 LED flashes to indicate that the gateway is sending data through the serial 

port.

R (Serial port Receive, Green) 

The R or 

r

eceive

 D

AtA

 LED flashes to indicate that the gateway is receiving data through the serial 

port.

Chassis Ground

Power Connection

Dip Switches

Hardware Reset Button

Summary of Contents for STRIDE SGW-MB1511-T

Page 1: ...This Chapter User Manual Overview 1 2 Introduction 1 3 Product Overview 1 3 Hardware 1 3 Hardware Reset Button 1 5 DIP Switches 1 5 LEDs 1 5 Installation DIN Rail Mounting 1 6 Dimensional Drawings 1 7...

Page 2: ...you cannot find the solution to your particular application or if for any reason you need additional technical assistance please call technical support at 770 844 4200 We are available weekdays from 9...

Page 3: ...sks to your processes and your equipment Security should always be carefully evaluated for each installation Refer to Appendix D Security Considerations for Control Systems Networks for more informati...

Page 4: ...Input Redundant input terminals Input Voltage 12 24 48 VDC Max Input Voltage Range 9 6 60 VDC Appliance Class Class III SELV power source Reverse Power Protection Yes Overload Protection Yes Environm...

Page 5: ...is one yellow SPEED LED for each Ethernet port LED ON indicates Ethernet speed is 100 Mbps LED OFF indicates Ethernet speed is 10 Mbps Link Activity RJ45 Green There is one green Link Activity LED for...

Page 6: ...nt when installed in Class 1 Division 2 Hazardous Locations The gateway can be snapped onto a standard 35mm x 7 5 mm height DIN rail Standard CENELEC EN50022 and can be mounted either vertically or ho...

Page 7: ...mensional Drawings NOTE Allow 20mm 0 79 clearance around each gateway for proper cooling Dimensions Part No Weight Width A Depth B Height C mm inches SGW MB1511 T 0 17 kg 0 36 lb 30 0 1 18 68 0 2 68 1...

Page 8: ...A recommended DC power supply is AutomationDirect com part number PSL 24 010 Terminal block connector is Degson 2EDGK 5 08 04P 14 1000AH or equivalent Ferrule required for stranded wire Wire Size Ran...

Page 9: ...und loops the cable shield should be tied to the metal connector body at one end of the cable only Electrical isolation is also provided on the Ethernet ports for increased reliability Ethernet Cable...

Page 10: ...ns a DIP switch selectable 120 Termination Resistor between RXD and RXD for each serial port when the Gateway is wired at one end of the serial network NC RS 422 RS 485 Gateway Slave 1 Slave 2 Last Sl...

Page 11: ...d store that data into gateway shared memory If a Modbus query comes in for one of those data points the gateway will immediately respond with the data it has stored and thereby respond much faster th...

Page 12: ...Chapter 1 Getting Started Page 1 12 Stride MB Gateway User Manual 1st Edition Rev E August 2020...