background image

3ph  typical tripping characteristics

Current (multiples  of  setting current)

Links BRX180 for independent use

4.

Manual or automatic reset

Set the adjustment dial.4 (fig.2) in the position of arrow as follows:

M= manual reset by means of pushbutton .4 (fig.2)
A= automatic reset

By operating the pushbutton .4 (fig.2) contact (95-96) closes, if tripped.
Automatic reset is not suggested for permanent contact control devices as, when the
tripping occurs, the motor is automatically reenergized after the cooling time of the relay.

5.

Function of the red stop pushbutton

Stop button .2 (fig.2) allow to open momentarily the contact (95-96) but it can't be used
to reset  the relays when tripped.

6.

Test before commissioning

Press pushbutton .4 (fig.2) to reset relay.  Move the actionator .3 (fig.2) in  direction
of arrow marked "TEST", the relay trips. NC contact (95-96) opens and NO  contact (97-
98) closes.  Trip indicator .3 
(fig.2) shows yellow for tripped condition.

7.

Fuse protection

Short circuit protection of the main poles is achieved by a back up fuse as indicated
on rating table.Short circuit protection of auxiliary contacts: 6AgG.

8.

Permissible ambient temperature

-25°C to +55°C temperature compensated.

Links BRP180 for direct connection to GH15NT and GH15PT contactors

Fig. 3

Fig. 4

Fig. 5

Average values at  20°C ambient
temperature, tripping  three-phase from cold
condition.
Proceeding  from service condition the times
decrease to 20-30% of the characteristic
values.

 Specifications are subject to change without notice

RTD180.120

RTD180.180

80-120A

120-180A

 BRP180 

    for direct connection to

GH15NT, GH15PT (fig.5)

RTD180.90

60-90A

without links (fig .3)

Relays type Setting range Links type supplied with O/L relays

Optional links type BRX180 are available for
independent use (fig.4).

Reviews: