DPM1 User Manual, 1st Edition
User Manual - DPM1 Series Panel Meters
18
Configuration Lock Out
The meter is delivered with the programming not locked out, giving access to all the
programming levels. Once completed the meter programming the following security measures
are recommended:
1. Lock out the programming access to prevent from programmed parameters modifications.
2. Lock out Key Pad functions to prevent from accidental modifications.
3. There are two lockout modes: selective and total. If the parameters are going to be readjusted
frequently, make a selective lockout. If no adjustment is going to be made, make a total
lockout. Key Pad functions lockout is always possible.
4. The access to the lockout routine is allowed by entering a personalized code. We recommend
changing the code set at factory and to write down your personalized code and keep it in a
safe place.
TOTAL LOCKOUT
The access to the programming routines to read data is allowed even if all parameters are locked
out ALL=Yes, but
it will not be possible to enter or modify data
. In this case, when entering
in the programming mode, the display shows the indication “
-dAtA-
”.
PARTIAL LOCKOUT
When only some parameters are locked out, all configuration data can be read but
only non
protected parameters can be modified
. In such case, when entering in the programming
mode, the display shows the indication
-Pro-
“.
Menus or submenus that can be locked out are:
• Relay 1 Configuration (C.SP.1).
• Relay 2 Configuration (C.SP.2).
• Relay 1 Setpoint Value (V.SP.1).
• Relay 2 Setpoint Value (V.SP.2).
• Input configuration (InP).
• Display (dSP).
• Analog output configuration (A.Out). If present in meter.
• Programming of the key TARE (tArE).
Lock-out menu diagram
The following figure shows the lock-out menu. The access to this menu is accomplished from
the run mode by pressing the
ENTER
key for 3 seconds, until the
“CodE”
indication appears.
The instrument is shipped from factory with the following default code:
“0000”
. Once this
code is entered, the
“CHAn”
menu is available to change to a personal code. Write down and