background image

Modulex Controller Operation

8

Figure 1-11. Location of BCM Address Selection Switch SW1

1.7.2 MONITORING AND CONFIGURATION

ONLY

For monitoring and configuration only, set the 3-position switch
to position II when the E8 is controlling the boiler. The boiler
operation can be monitored via the Modbus terminals.

1.7.3 MODBUS DIRERCT DRIVE CONTROL

AND MONITORING

The BCM’s modulation output can be directly driven by writing
to its Direct Drive register (Standard Holding Register). It
will ramp up the boiler based on the settings in the Standard
Holding Register or Setting Register 3000 to 3051. The default
maximum setpoint temperature limit is 85°C as shown in
register 3015. This value should not be increased, if possible.
The default timeout interval is 30 seconds as shown in register
3011. To prevent communication dropouts, write the direct
drive modulation value at least 3 times within the
communication timeout interval.

1.7.4 MODBUS REMOTE SETPOINT

CONTROL AND MONITORING

To send a setpoint temperature to the BCM and have it control
the boiler based on its internal settings, 3 registers need to be
adjusted:

1. the desired setpoint should be written to the Requested

Setpoint (Address 1004)in the Standard holding Registers
or Control Registers. This value should be written at least
3 times within the Communication Timeout time (Address
3011).

2. The Heat Request Command (Control Register Address

1021) should be set to 0xEE (238) to request heat.

3. If the modulation level should be allowed to go above

50%, adjust the Maximum Modulation Level setting (Ad
dress 1017).

NOTE

If power is lost, all Control Register settings re-
turn to their default values. Be sure to read them

regularly and refresh if necessary. The changes
to the Settings Registers are stored during

power-down.

1.7.5 EMS OR BAS SET-UP AS MASTER TO

BCM CONTROLLER SLAVES

Ref

u

er to the set-up instructions in the man facturer’s equip-

ment manual for the Energy Management System (EMS) or
Building Automation System (BAS) being used as the control-
ling Master.

1.7

MODBUS SOFTWARE SET-UP

The following paragraphs provide the information and proce-
dures necessary to configure the Boiler Communications
Modules (BCMs) to operate on a Modbus Network.

NOTE

The following paragraphs assume that between
1 and 9 Modulex Boilers are being controlled on
the Modbus Network.

7.7.1 BCM Set-Up for Modbus Operation

The BCM Controller can be set up for the following types of
Modbus operating modes:

• Monitoring and Configuration Only
• Modbus Direct Drive Control and Monitoring
• Modbus Remote Setpoint Control and Monitoring

In order for the BCM Controller to be recognized by the Mod-
bus Master, a valid address must be set at each BCM on the
Modbus Network. Address selection on each BCM is accom-
plished by setting rotary DIP switch SW1. This switch is loca-
ted in the lower right portion of each BCM as shown in Figure
1-11.

As Figure 1-11 shows, SW1 is a 10-position switch labeled 0
– 9. SW1 is set to the desired position using a small flat-tip
screwdriver. Figure 1-11 shows SW1 set to address 0 (zero)
which disables the BCM on the Modbus Network. Only Mod-
bus addresses 1 through 9 will be recognized by the Modbus
Master. SW1 must be set to a different position for each Modu-
lex Boiler being controlled on the Modbus Network.

Once the desired address has been set on each BCM, the
Modulex Boiler is configured for Modbus Network control by
the controlling Master EMS/BAS. In order for the BCM to act as
the Back-Up Controller if the Modbus Master signal is lost, the
ENABLE/DISABLE switch must be set to ENABLE (1).
See Appendix B for Modbus points for the BCM.

Summary of Contents for BCM

Page 1: ...Operating Instructions Modulex Boiler Communications Module BCM ...

Page 2: ...ctions are illustrated and described in Figure 1 2 The Modulex Boiler is shipped with the BCM a third Control Switch is mounted above the BCM This switch is used to enable disable the e Bus connection between the E8 and BCM Controllers Refer to paragraph 1 4 3 for details Figure 1 2 BCM Controls and Indicators CONTROL INDICATOR ENABLE DISABLE SWITCH I 0 RESET SWITCH DL1 Yellow LED DL2 Red LED DL3 ...

Page 3: ...at Figure 1 4 BCM Back Up Controller Wiring 1 3 BCM CONFIGURED AS BACK UP CONTROLLER When the BCM is configured as the Back Up Controller for the E8 it will assume control of the Modulex Boiler if the E8 fails In the event of an E8 Controller failure the BCM will operate the Modulex Boiler in the Constant Setpoint Mode default setpoint C The primary Boiler 82 Pump must also be wired to the BCM so ...

Page 4: ...are provided in Appendix B of this document 1 4 1 OPERATING SCENARIO Each Modulex Boiler is equipped with its own BCM to allow Modbus Network monitoring and control The Master can control the Networked Modulex Boilers utilizing either Remote Setpoint or Modulation Level signaling In the event that the external control signal from the EMS or BAS is lost the BCM will assume control of the Modulex Bo...

Page 5: ... position ON OFF switch on the BCM BCM 2 Postion ON OFF Switch I 1b See NOTE 1 Below O 0 See NOTE 2 Below II 1a See NOTE 3 Below The BCM is the Gate way for Mo dbus and external control The E8 does not control the boiler and the BCM will not take over the boiler if the Modbus signal fails The BCM is the Gate way for Mo dbus and external control The E8 does not control the boiler and the BCM will t...

Page 6: ... only as Slave devices on a Modbus Network Since the Slaves are connected in a Daisy Chain configuration the terminating resistor must be enabled only in the last BCM Controller in the chain Enabling the terminating resistor is accomplished by positioning jumper JP1 as shown in Figure 1 9 only on the BCM Board contained in the last BCM Controller As mentioned in paragraph 1 5 1 when the controllin...

Page 7: ...7 ...

Page 8: ...essary The changes to the Settings Registers are stored during power down 1 7 5 EMS OR BAS SET UP AS MASTER TO BCM CONTROLLER SLAVES Ref u er to the set up instructions in the man facturer s equip ment manual for the Energy Management System EMS or Building Automation System BAS being used as the control ling Master 1 7 MODBUS SOFTWARE SET UP The following paragraphs provide the information and pr...

Page 9: ...edium EMS Master to BCM Slave RS 485 Alowable Cable Length Address Support From Master EMS T rasmission Mode Support Timing specifications Baud Rate Data Framing Message Framing Character Framing Heartbeat Timeout DESCRIPTION B 1 2 Modbus Support Requirements The Modb r m to the suppor us Netwo k must confor t requirements listed in T able B 2 RS485 2 Wire Differential Bus With Shield 4000 Feet Ma...

Page 10: ...sidual flame 42 Outlet temperature sensor fault 38 Other conditions not listed above enum 1 3 5 1 Standby ready to run but not fired 3 Remote fired 5 Fault failure detected B 2 2 BCM CONTROLLER STANDARD HOLDING REGISTER ASSIGNMENTS The BCM Controller Holding Registers contain functions that are Read Only Write Only or both Read Write The address assignments for these functions are listed in T able...

Page 11: ...11 Table B 4 BCM Standard Holding Register Address Mapping ...

Page 12: ...Modulex Controller Operation Appendix B 12 Table B 4 BCM Standard Holding Register Address Mapping Cont ...

Page 13: ...13 Table B 4 BCM Standard Holding Register Address Mapping Cont APPENDIX B ...

Page 14: ...Modulex Controller Operation Appendix B 14 Table B 4 BCM Standard Holding Register Address Mapping Cont APPENDIX B ...

Page 15: ... utomatic Heating P Ltd ABN 90 446 545 923 DISTRIBUTED BY Telephone Facsimile Email 1800 337 959 61 3 9310 5655 sales automaticheating com au P O Box 35 Epping VIC 3076 Australia www automaticheating com au ...

Reviews: