Automated Logic UNI/59 Technical Instructions Download Page 5

Revised 1/3/01 • UNI/59

5

© 2001 Automated Logic Corporation

Make sure that all T-Line or U-Line modules 
and the TNPB use the same polarity 
throughout the subnet. You can verify that the 
UNI/59 is communicating with the subnet by 
making sure the Unet transmit and receive 
LEDs are active.

When adding a new T-Line or U-Line module 
to an existing subnet, you must transfer 
memory to the UNI/59 before the new card is 
recognized.

Connecting the UNI/59 to the CMnet

When communicating on an ARC156 CMnet, 
use an A3ARC156 wire available from 
Magnum Cable Corp. Use a dedicated 22AWG 
to 18AWG twisted pair wire for legacy CMnet 
(EIA-485) wiring. For more information about 
CMnet wiring, refer to the 

Technical Handbook

 

or to the 

ARC156 CMnet Wiring Technical 

Instructions.

To set the baud rate at 156 kbps (when using 
an ARC156 CMnet), set the baud rate jumper 
to Arc156 (see Figure 5).

To set the baud rate at 38.4 kbps, set the baud 
rate jumper to 9600/38.4K, and set the first 
switch on the eight-position DIP switch to 
38.4K (see Figure 6).

To set the baud rate at 9600 bps, set the baud 
rate jumper to 9600/38.4K, and set the first 
switch on the eight-position DIP switch to 
9600 (see Figure 6).

You can verify that the UNI/59 is 
communicating on the CMnet by making sure 
the CMnet transmit and receive LEDs are 
active.

Addressing

The UNI/59 has an eight-position DIP switch 
for assigning the module’s CMnet address. 
Before setting or changing the address, make 
sure the UNI/59’s power is off, since the 

 Figure 3. Communication wiring 

 Figure 4. Unet configuration jumpers

NET+
NET -

NET+

NET-

NET+
NET-

   

   

N /C

E IA-48 5

U N I

N /C

N /C

 Figure 5. Setting the CMnet baud rate to 156 

kbps

 Figure 6. Setting the CMnet port baud rate to 

38.4 kbps or 9600 bps

 

 

  





38.4k

Summary of Contents for UNI/59

Page 1: ...r brand and product names are trademarked by their respective companies Technical Instructions UNI 59 Using the UNI 59 2 Specifications 2 Mounting 3 Power Wiring 3 Communicating with the UNI 59 3 Conn...

Page 2: ...document at http www automatedlogic com or the SupportPlus CD for more information Make sure you use the correct module driver for your application CAUTION Changes or modifications to this unit not ex...

Page 3: ...100VA maximum Take appropriate isolation measures when mounting the UNI 59 module in a control panel where non Class 2 devices 120VAC or greater or wiring are present You can power several modules fr...

Page 4: ...modules The UNI 59 supports up to 59 T Line or U Line modules If you are using T Line modules you must use a REPOPT repeater after every 20 modules on the Unet If you are using U Line modules you must...

Page 5: ...To set the baud rate at 156 kbps when using an ARC156 CMnet set the baud rate jumper to Arc156 see Figure 5 To set the baud rate at 38 4 kbps set the baud rate jumper to 9600 38 4K and set the first...

Page 6: ...e UNI 59 s module driver and look at the module status report in SuperVision to make sure the module type and number agree with the module The module type for the UNI 59 is 76 To view the module statu...

Page 7: ...ur own cable use the diagrams in Figure 8 3 Set up your communications program with the correct COM port and baud rate settings to display the diagnostic information output by the UNI 59 The diagnosti...

Page 8: ...tch s position turn the UNI 59 module off first Once you have adjusted the switch turn the module back on 1 Connect the computer s serial port to the EIA 232 port of the APT using a standard straight...

Page 9: ...ains the Run and Error LED signals in detail to assist troubleshooting Power indicates power is being supplied to the module CMnet Tx lights when the module transmits data over the CMnet CMnet Rx ligh...

Page 10: ...ticker on the back of the module also shows the date the module was manufactured The first three characters on the sticker indicate the type of module The next two characters show the year and month o...

Reviews: