Using the S6104

The S6104 is part of the S-Line, designed 
specifically for controlling rooftop Air 
Handling Units (AHUs). The module can be 
mounted directly in or on the rooftop 
equipment. 

The table below outlines the limitations and 
requirements depending on whether you are 
using WebCTRL or SuperVision to 
communicate with your S6104.  

For more information, see the appropriate 
module driver document on the Automated 
Logic website at www.automatedlogic.com.

The S6104 has:

• 6 digital outputs

• 10 universal inputs

• 4 analog outputs

A single board provides the power circuitry, 
microprocessor, and non-volatile memory 
(stores data even during a power failure). The 
Access Port allows communication with 
WebCTRL or SuperVision. The 4-pin LogiStat 
Port provides the interface for a LogiStat 
room sensor. With certain restrictions, the 
LogiStat Port can also be used to 
communicate with WebCTRL or

 

SuperVision

 

(see Figure 1). 

 

WebCTRL

SuperVision

Module Driver

DRV_S6104

SLM

Number of Function 
Blocks*

1

1

Number of BACnet 
Objects*

1000

1000

* depending on available memory

 Figure 1. S6104 Dimensions and Layout

7 1 /2 "

1 9 c m

1 1 /8 "

2 .8 5 8 c m

D u a l R o ta ry

A d d re s s S w itc h e s

D ig ita l O u tp u t M o d e

(H O A ) S w itc h e s

P o w e r

S w itc h

A c c e s s

P o rt

8 7 /8 "

2 2 .5 4 3 c m

1 1 /4 "

1 /4 "

.6 3 5 c m

M a n u a l F o rm a t

B u tto n

3 .1 7 5 c m

L o g iS ta t P o rt

Summary of Contents for S6104

Page 1: ...ounting 3 Addressing 3 Power Wiring 4 Network Communications 4 Using the S6104 on an ARC156 Segment 5 Using the S6104 on a Legacy CMnet 5 Connecting the S6104 to the Network 5 Communicating with the W...

Page 2: ...log outputs A single board provides the power circuitry microprocessor and non volatile memory stores data even during a power failure The Access Port allows communication with WebCTRL or SuperVision...

Page 3: ...Outputs 6 digital outputs Form A 3A max Analog Outputs 4 analog outputs 0 to 10VDC 20mA source capability Output resolution 8 bit D A Communication For WebCTRL 156 kbps BACnet over ARCNET and 9600 bp...

Page 4: ...he S6104 has an operating range of 21 6VAC to 26 4VAC If voltage measured at the module s power input terminals is outside this range the module may not work properly 1 Turn the module s power off Thi...

Page 5: ...lect jumper must also be set to Access NOTE Setting the CMnet jumper to Legacy disables the industry standard BACnet over ARCNET ARC156 protocol for the network segment and enables the proprietary ALC...

Page 6: ...ommunication speed is fixed at 1200 baud 1 Connect the computer s serial port to the EIA 232 port of the APT using a standard straight through cable 2 Set the APT s Mode Select switch to TTL see Figur...

Page 7: ...rt when finished to allow the S6104 to receive inputs from the LogiStat Communicating Through the Access Port Using SuperVision When using SuperVision you can connect a workstation or portable compute...

Page 8: ...ource to power the 4 20mA transducer The B terminal is capable of supplying 18 to 24VDC but the total current of all B terminals must not exceed 200mA If the voltage measured from the B terminal to Gn...

Page 9: ...e of sensor used Make sure the jumper is positioned correctly and be sure to grip the jumper by the sides only See Figure 10 Figure 8 Input Wiring 15 16 17 18 20 19 14 13 12 11 10 9 8 7 6 5 4 3 2 1 IN...

Page 10: ...pin 2 Temp of the LogiStat Port The LogiStat Plus also provides the slidepot position and TLO inputs through pin 3 Sw The LogiStat Pro provides temperature setpoint adjust and TLO inputs through seria...

Page 11: ...mode by setting the HOA switches see Figure 1 on page 2 for the switches location Table 5 on page 12 shows the status of the digital output based on the output s configuration and the HOA switch posit...

Page 12: ...put s operation lock the output to a known condition using the Function Block s Properties page in WebCTRL or Parameter page in SuperVision Be sure the equipment operates as specified Writing GFBs for...

Page 13: ...pend on the type of sensor or actuator attached to the I O point You can select the channel number offset and gain using SuperVision s Point Help feature or Configure Points utility Alternatively you...

Page 14: ...ute Download button If any downloads failed they are listed in the Failures section under the tree in the UI 2 Thermistor 32 17 to 213 F 27 to 100 6 C 0 00 0 00 15 88 15 69 mA or Volts 32 0 to 20mA 0...

Page 15: ...SC key type MO module address 15 and press Enter 3 Transfer memory to the module In SuperVision v3 0 click Tools Troubleshooting Transfer Memory to Module In SuperVision v2 6b download memory for This...

Page 16: ...imal Figure 17 S6104 LED locations Table 9 LED Signals Run LED Error LED Condition 2 flashes per second Off Normal 2 flashes per second 1 flash then pause Normal but module is alone on the CMnet this...

Reviews: