Automated Logic S6104 Technical Instructions Download Page 16

Revised 7/30/02 • S6104

16

© 2002 Automated Logic Corporation

Power - indicates power is being supplied to 
the module.

CMnet Tx - lights when the module transmits 
data over the CMnet.

CMnet Rx - lights when the module receives 
data from the CMnet.

Digital Output Status - lights when the digital 
output is activated.

Analog Output Status - lights when the 
analog output is activated.      

Protection

The S6104 module is protected by internal 
solid state Polyswitches on the incoming 
power and network connections. These 
Polyswitches are not replaceable and will 
reset themselves if the condition that caused 
the fault returns to normal.

Production Date

To determine when a module was 
manufactured, check the module status 
report for the module in WebCTRL or 
SuperVision. Refer to the appropriate user’s 
guide for more information about the module 
status report.

A sticker on the back of the module also 
shows the date the module was 
manufactured. The first three characters on 
the sticker indicate the type of module. The 
next two characters show the year and month 
(the month digit is in hexadecimal).

 Figure 17. S6104 LED locations

Table 9. LED Signals

Run LED

Error LED

Condition

2 flashes 
per second

Off

Normal

2 flashes 
per second

1 flash, 
then pause

Normal, but module is 
alone on the CMnet       
(this sequence doesn’t 
occur in WebCTRL)

2 flashes 
per second

2 flashes 
alternating 
with LED

Five minute auto-restart 
delay after system error

2 flashes 
per second

2 flashes in 
sync with 
LED, then 
pause

Module is configured for a 
different baud rate than the 
rest of the network 
segment

2 flashes 
per second

3 flashes, 
then off

Module has just been 
formatted

Digital Output

Status

Run

Error

CMnet

Tx

CMnet

Rx

Analog Output

Status

Power

C O R P O R A T I O N

O GIC

L

U TO M A T E D

A

1 1

1 2

S6104

Control Module

2 flashes 
per second

4 flashes, 
then pause

Two or more devices on 
this network have the 
same ARC156 network 
address

2 flashes 
per second

On

Exec halted after frequent 
system errors or GFBs 
halted

5 flashes 
per second

On

Exec start-up aborted, Boot 
is running

5 flashes 
per second

Off

Firmware transfer in 
progress, Boot is running

7 flashes 
per second

7 flashes 
per second, 
alternating 
with LED

Ten second recovery 
period after brownout

14 flashes 
per second

14 flashes 
per second, 
alternating 
with LED

Brownout

Table 9. LED Signals (Continued)

Run LED

Error LED

Condition

Summary of Contents for S6104

Page 1: ...ounting 3 Addressing 3 Power Wiring 4 Network Communications 4 Using the S6104 on an ARC156 Segment 5 Using the S6104 on a Legacy CMnet 5 Connecting the S6104 to the Network 5 Communicating with the W...

Page 2: ...log outputs A single board provides the power circuitry microprocessor and non volatile memory stores data even during a power failure The Access Port allows communication with WebCTRL or SuperVision...

Page 3: ...Outputs 6 digital outputs Form A 3A max Analog Outputs 4 analog outputs 0 to 10VDC 20mA source capability Output resolution 8 bit D A Communication For WebCTRL 156 kbps BACnet over ARCNET and 9600 bp...

Page 4: ...he S6104 has an operating range of 21 6VAC to 26 4VAC If voltage measured at the module s power input terminals is outside this range the module may not work properly 1 Turn the module s power off Thi...

Page 5: ...lect jumper must also be set to Access NOTE Setting the CMnet jumper to Legacy disables the industry standard BACnet over ARCNET ARC156 protocol for the network segment and enables the proprietary ALC...

Page 6: ...ommunication speed is fixed at 1200 baud 1 Connect the computer s serial port to the EIA 232 port of the APT using a standard straight through cable 2 Set the APT s Mode Select switch to TTL see Figur...

Page 7: ...rt when finished to allow the S6104 to receive inputs from the LogiStat Communicating Through the Access Port Using SuperVision When using SuperVision you can connect a workstation or portable compute...

Page 8: ...ource to power the 4 20mA transducer The B terminal is capable of supplying 18 to 24VDC but the total current of all B terminals must not exceed 200mA If the voltage measured from the B terminal to Gn...

Page 9: ...e of sensor used Make sure the jumper is positioned correctly and be sure to grip the jumper by the sides only See Figure 10 Figure 8 Input Wiring 15 16 17 18 20 19 14 13 12 11 10 9 8 7 6 5 4 3 2 1 IN...

Page 10: ...pin 2 Temp of the LogiStat Port The LogiStat Plus also provides the slidepot position and TLO inputs through pin 3 Sw The LogiStat Pro provides temperature setpoint adjust and TLO inputs through seria...

Page 11: ...mode by setting the HOA switches see Figure 1 on page 2 for the switches location Table 5 on page 12 shows the status of the digital output based on the output s configuration and the HOA switch posit...

Page 12: ...put s operation lock the output to a known condition using the Function Block s Properties page in WebCTRL or Parameter page in SuperVision Be sure the equipment operates as specified Writing GFBs for...

Page 13: ...pend on the type of sensor or actuator attached to the I O point You can select the channel number offset and gain using SuperVision s Point Help feature or Configure Points utility Alternatively you...

Page 14: ...ute Download button If any downloads failed they are listed in the Failures section under the tree in the UI 2 Thermistor 32 17 to 213 F 27 to 100 6 C 0 00 0 00 15 88 15 69 mA or Volts 32 0 to 20mA 0...

Page 15: ...SC key type MO module address 15 and press Enter 3 Transfer memory to the module In SuperVision v3 0 click Tools Troubleshooting Transfer Memory to Module In SuperVision v2 6b download memory for This...

Page 16: ...imal Figure 17 S6104 LED locations Table 9 LED Signals Run LED Error LED Condition 2 flashes per second Off Normal 2 flashes per second 1 flash then pause Normal but module is alone on the CMnet this...

Reviews: