Page 57
The 2x Read addresses give analogue inputs. Refer to section 4.5.2 for relevance of these addresses.
For example if Modbus address 30602 outputs reads as 2.0 then E.G.A. ID 1 has online O
2
value of
2%.
2x
读取地址给出模拟输入。关于该类地址请参考
4.5.2
章节。例如:如果
Modbus
地址
30602
输出读取为
2.0
,则尾气分析仪
ID1
有
2%
的在线
O2
值。
3x Read
3x
读取
E.G.A. ID
尾气分析仪
ID
1
2
3
4
5
6
7
8
9
10
Fuel Selected
选择的燃料
30601
30621
30641
30661
30681
30701
30721
30741
30761
30781
% O2
30602
30622
30642
30662
30682
30702
30722
30742
30762
30782
% CO2
30603
30623
30643
30663
30683
30703
30723
30743
30763
30783
CO ppm
30604
30624
30644
30664
30684
30704
30724
30744
30764
30784
NO ppm
30605
30625
30645
30665
30685
30705
30725
30745
30765
30785
SO2 ppm
30606
30626
30646
30666
30686
30706
30726
30746
30766
30786
Exhaust
Temperature
排气温度
30607
30627
30647
30667
30687
30707
30727
30747
30767
30787
Efficiency
效率
30608
30628
30648
30668
30688
30708
30728
30748
30768
30788
Error number
故障数
30609
30629
30649
30669
30689
30709
30729
30749
30769
30789
% Voltage
input
%
电压输入
30610
30630
30650
30670
30690
30710
30730
30750
30770
30790
Delta
Temperature
Delta
温度
30611
30631
30651
30671
30691
30711
30731
30751
30771
30791
Ambient
Temperature
环境温度
30612
30632
30652
30672
30692
30712
30732
30752
30772
30792
Auxiliary
Temperature
辅助温度
30613
30633
30653
30673
30693
30713
30733
30753
30773
30793
Service LEDs
服务发光二级管
30614
30634
30654
30674
30694
30714
30734
30754
30774
30794