USER MANUAL TRAVEL CHARGER
12
WARNING!
Only qualified personnel can prepare the connection point for the charging
station.
The charging station is connected to a 400 V AC power supply network according to the TN-S
scheme (L1 + L2 + L3 + N + PE). When connecting with a 4-wire cable, carry out the protective
grounding with a separate wire. It is necessary to install an AC circuit breaker between the
station and the power supply network when the power cable laying. It is recommended to use
a 4-pole 63 A circuit breaker.
To connect the charging station, it is necessary to prepare a cable installation with a cross-
section of at least 5x10 mm
2
(30 kW) or 5x16 mm
2
(40 kW) and install a CEE socket (5 pin, 63 A).
4.3 STATION CONNECTING
The charger does not require any special adjustment or tuning before it is put into operation.
ATTENTION!
DO NOT SWITCH ON THE CHARGER WITHOUT A CONNECTED
GROUNDING!
Non-compliance with this requirement may result in energizing the charger body, electric
shock damage to the service personnel and consumers, as well as in a failure of the charger.
To connect the charging station to the electric circuit, it is necessary to put the device power
cable plug into the socket and switch the station circuit breakers to the working position. Next,
move the external circuit breaker to the operating position.
In the case when the station will connect to the control server, it is necessary to:
•
Install
mobile operator’s
SIM-card (if an external SIM-card is used):
-
remove the modem cover;
-
install SIM-card;
-
close the modem cover.
•
Move the circuit breakers to the operating position (up).
•
Move the circuit breaker on the switch board to the operating position (up).