Appliance specifications

Table 4: Environmental specifications

Rated voltage range

Special application 17 - 31 VRMS

Temperature range

32° F to 120° F (0° C to 49° C)

Humidity range

10% to 93%, non-condensing at 104° F (40° C)

Connections

Terminal for 18 AWG to 12 AWG (0.82 mm² to 3.31 mm²)

Table 5: Sound pressure level measurement (dBA)

Reverberant Room at 10 Feet

in accordance with UL464 (See

Note 2)

Voltage (Vrms)

Horn mode steady

Horn mode coded (see note 1)

High volume setting using

addressable controller (See Note 3)

17 (Min.)
23
31 (Max.)

87.6
89.8
91.9

83.1
86
86

Low volume setting using

addressable controller (See Note 3)

17 (Min.)
23
31 (Max.)

80.6
83.4
86.2

76.9
79.2
82.3

Anechoic Room at 10 feet in accordance with ULC S525, see note 4.

High volume setting

17 (Min.)
23
31 (Max.)

89.9
92.5
94.4

89.6
92.4
93.9

Low volume setting

17 (Min.)
23
31 (Max.)

84.1
86.7
89.1

83.6
86.6
88.6

Note:

1. The coded category covers both Temporal and March time cadences.

2. Reverberant dBA measurements are a minimum UL rating based on sound power level measurements made in UL’s reverberant test chamber.

3. High and low volume settings are configured with DIP switch (CFIG1) on the controller.

4. If you install the A4905-9838 Sound Damper, the anechoic measurements decrease by approximately 9 dBA.

Table 6: Current draw

Application

Appliance type

Maximum RMS current

UL464/ULCS525 (0° C TO 50° C)

AO

23 mA

Table 7: ULC directional characteristics for horn

Access

Angle

dBA

61.5° left and right

-3 dBA

Horizontal

90° left and right

-4.6 dBA

62° up and down

-3 dBA

Vertical

90° up and down

-3.8 dBA

CAUTION:

• The appliances are available in red and white. Do not paint or otherwise alter the factory finishes in any way.
• Anechoic dBA levels below 85 do not meet ULC requirements for public notification.

Summary of Contents for A49AO-APPLW

Page 1: ...e Colors Models Operation Wall Mount Horn Audible Only AO Red White Components A49AO APPLW Backplate A49MP AVVOWR A49MP AVVOWW Covers A49AOC WRFIRE A49AOC WRS A49AOC WWFIRE A49AOC WWS These appliances provide an audible AO warning of an alarm condition when activated from the control panel of a compatible UL ULC Listed Autocall Fire Alarm System Note For information about TrueAlert ES appliance te...

Page 2: ...A O A O A O A O A O A O A O From a compatible SLC controller see notes Class B wiring see notes To the next appliance or compatible SLC controller see notes 100 Fig 2 Wiring Instructions Wiring notes The maximum number of appliances on a circuit or on an IDNAC SLC is 127 The maximum wire resistance between appliances is 26 ohms See the field wiring diagrams for the driving compatible fire alarm co...

Page 3: ...dress 7 Not used 001 101 011 111 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 DIP SWITCHES 5 THROUGH 7 000 100 010 110 Fig 3 Setting the DIP Switch Address Setting the horn configuration switch Certain options for the horn ca...

Page 4: ...le controller See Note 3 17 Min 23 31 Max 87 6 89 8 91 9 83 1 86 86 Low volume setting using addressable controller See Note 3 17 Min 23 31 Max 80 6 83 4 86 2 76 9 79 2 82 3 Anechoic Room at 10 feet in accordance with ULC S525 see note 4 High volume setting 17 Min 23 31 Max 89 9 92 5 94 4 89 6 92 4 93 9 Low volume setting 17 Min 23 31 Max 84 1 86 7 89 1 83 6 86 6 88 6 Note 1 The coded category cov...

Reviews: