Appliance specifications
Table 4: Environmental specifications
Rated voltage range
Special application 17 - 31 VRMS
Temperature range
32° F to 120° F (0° C to 49° C)
Humidity range
10% to 93%, non-condensing at 104° F (40° C)
Connections
Terminal for 18 AWG to 12 AWG (0.82 mm² to 3.31 mm²)
Table 5: Sound pressure level measurement (dBA)
Reverberant Room at 10 Feet
in accordance with UL464 (See
Note 2)
Voltage (Vrms)
Horn mode steady
Horn mode coded (see note 1)
High volume setting using
addressable controller (See Note 3)
17 (Min.)
23
31 (Max.)
87.6
89.8
91.9
83.1
86
86
Low volume setting using
addressable controller (See Note 3)
17 (Min.)
23
31 (Max.)
80.6
83.4
86.2
76.9
79.2
82.3
Anechoic Room at 10 feet in accordance with ULC S525, see note 4.
High volume setting
17 (Min.)
23
31 (Max.)
89.9
92.5
94.4
89.6
92.4
93.9
Low volume setting
17 (Min.)
23
31 (Max.)
84.1
86.7
89.1
83.6
86.6
88.6
Note:
1. The coded category covers both Temporal and March time cadences.
2. Reverberant dBA measurements are a minimum UL rating based on sound power level measurements made in UL’s reverberant test chamber.
3. High and low volume settings are configured with DIP switch (CFIG1) on the controller.
4. If you install the A4905-9838 Sound Damper, the anechoic measurements decrease by approximately 9 dBA.
Table 6: Current draw
Application
Appliance type
Maximum RMS current
UL464/ULCS525 (0° C TO 50° C)
AO
23 mA
Table 7: ULC directional characteristics for horn
Access
Angle
dBA
61.5° left and right
-3 dBA
Horizontal
90° left and right
-4.6 dBA
62° up and down
-3 dBA
Vertical
90° up and down
-3.8 dBA
CAUTION:
• The appliances are available in red and white. Do not paint or otherwise alter the factory finishes in any way.
• Anechoic dBA levels below 85 do not meet ULC requirements for public notification.