background image

Page 3

579-1034AC  Rev G

TrueAlert ES Addressable Indoor A/O Notification Appliances Installation Instructions

Setting the address DIP Switch

Each addressable TrueAlert ES notification appliance has a unique address that is set using an eight position DIP switch (ADDR1). Assign up to 127

unique addresses to an SLC, however, the total appliance loading available may be less due to appliance current requirements.
To set the address, complete the following steps:

1.

Insert a number 1 or number 2 Phillips screwdriver, or a similar sized object, into the opening at the bottom of the appliance and unclip the

appliance from the backplate. See Figure 3.

2.

Set the switches using a non-metallic stylus, or the equivalent.

3.

Record the set address.

To access the switches: 

ADDR1

The DIP switch shown is

set at address 7

Not used

001

101

011

111

64
65
66
67
68
69
70

71
72

73
74

75

76

77
78
79

80
81
82
83
84
85
86
87
88
89
90
91
92
93

94
95

96
97
98
99

100
101
102
103
104
105
106
107
108
109
110
111

112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127

DIP SWITCHES 5 THROUGH 

7

000

100

010

110

Fig 3: Setting the DIP Switch Address

Setting the horn configuration switch

Certain options for the horn can be configured directly on the appliance using the Configuration switch (CFIG1) on the back of the appliance. See

Figure 4.

Table 3: AO Settings

Position 1

Configuration Control: OFF to enable Local Audible control

(positions 2-7 below), ON for Panel control.

Position 2

Audible Volume: High (OFF), Low (ON).

Position 3

CAN Horn mode: switch must be set to OFF.

Position 4

Legacy NAC mode: switch must be set to OFF.

Position

5, 6, 7, 8

These switches are unused by the horn. Leave them set to

OFF.

To access the switches: 

CFIG1

          Device 

configuration switch

Not used (Leave at OFF)

Fig 4: Setting the

Appliance Configuration

Summary of Contents for A49AO-APPLW

Page 1: ...e Colors Models Operation Wall Mount Horn Audible Only AO Red White Components A49AO APPLW Backplate A49MP AVVOWR A49MP AVVOWW Covers A49AOC WRFIRE A49AOC WRS A49AOC WWFIRE A49AOC WWS These appliances provide an audible AO warning of an alarm condition when activated from the control panel of a compatible UL ULC Listed Autocall Fire Alarm System Note For information about TrueAlert ES appliance te...

Page 2: ...A O A O A O A O A O A O A O From a compatible SLC controller see notes Class B wiring see notes To the next appliance or compatible SLC controller see notes 100 Fig 2 Wiring Instructions Wiring notes The maximum number of appliances on a circuit or on an IDNAC SLC is 127 The maximum wire resistance between appliances is 26 ohms See the field wiring diagrams for the driving compatible fire alarm co...

Page 3: ...dress 7 Not used 001 101 011 111 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 DIP SWITCHES 5 THROUGH 7 000 100 010 110 Fig 3 Setting the DIP Switch Address Setting the horn configuration switch Certain options for the horn ca...

Page 4: ...le controller See Note 3 17 Min 23 31 Max 87 6 89 8 91 9 83 1 86 86 Low volume setting using addressable controller See Note 3 17 Min 23 31 Max 80 6 83 4 86 2 76 9 79 2 82 3 Anechoic Room at 10 feet in accordance with ULC S525 see note 4 High volume setting 17 Min 23 31 Max 89 9 92 5 94 4 89 6 92 4 93 9 Low volume setting 17 Min 23 31 Max 84 1 86 7 89 1 83 6 86 6 88 6 Note 1 The coded category cov...

Reviews: