DCU 205 User’s Manual
- 15 -
8.
R
EMOTE CONTROL
The Control Unit has wire terminals for two remote start and stop
alternatives.
•
Manual start and stop
•
Automatic start and delayed stop
8.1.
Manual start and stop
The Unit has terminals for remote start and stop. They work in the same
way as the local push buttons.
Remote Start is connected to terminals no. 18-19. Remote Stop is
connected to terminals no. 18-20.
Remember, a brief press on the stop button is enough to stop the engine.
8.2.
Automatic start, delayed stop
When the Control Unit is set in the STANDBY mode, an internal start/stop
program can be activated by means of external signals. Closed contact
between terminals no. 21-22 activates start, and closed contact between
terminals no. 21 and 23 activates stop.
For a more in-depth description of the above, see section 4.3,
Standby
, on
page 7.