- 12 -
LIPROMA3-00
- 12 Pr
oportion
al output setting procedure (REMOTE
SET UP)
-
Inputs
When each of these three inputs is active the values of the proportional outputs
changes overriding the function of the speed selector (if present on the transmitting
unit).
12
PROPORTIONAL OUTPUT SETTING PROCEDURE (REMOTE
SET UP)
Calibration of the proportional outputs must only be set by qualified
and trained personnel who understand and respect all the warnings
given in chapters 4, 5, 6 and 7.
The proportional outputs of RI97-08PVZA module are programmed at the values giv-
en on the relevant technical data sheet.
Never leave the DIP 1 in ON when the radio remote control is work-
ing: this position is compulsory during the calibration phase and,
when inserted, only one proportional command can be activated at
a time.
Preparation
for calibration
1. Make sure that the transmitting unit is switched off.
2. Remove power from the receiving unit.
3. Open the receiving unit and position the DIP 1 in ON.
4. Power the receiving unit.
5. Switch on and start up the transmitting unit.
6. Turn the starting keyswitch to the “
” (REMOTE SET UP) position.
Calibration
7. Select one or more positions of the rotary switch S on the RI97-08PVZA module
to calibrate the related parameters.
8. Operate the RPM+/- selector on the transmitting unit (where the + increases the
speed that is being calibrated and - decreases it).
Moving the joystick outside of the standstill position during the cal-
ibration, a horn/alarm sounds for 0.5 seconds signalling that the
minimum calibration zone is approaching.
If a speed selector with 2 or more pre-set levels is present on the
transmitting unit, calibration is to be performed for each of the se-
lector positions.
If the RI97-08PVZA module inputs are used on the receiving unit,
calibration is performed for each of these inputs activating them in
sequence.
Signal type
LEDs
red
green
yellow
Steady light
/
/
the initial values of
the proportional out-
put are reset when
the restore
pushbutton P
is pressed
Blinking
data memory
is damaged
the RI97-08PVZA
module is powered
and functioning *
the REMOTE SET UP
function is active
(DIP 1 is ON)
Light
switched off
the data memory is
functioning
the RI97-08PVZA
module is not
powered and
is not functioning
the REMOTE SET UP
function is not active
(DIP 1 is OFF)
* if the blinking is slow, there is no radio link
between the transmitting and the receiving unit