© Austria Email AG
20
V1.0 1/2021
If the heat pump extracts heat from the surrounding air, the room size must be at least 30 m
3
.
Maximum length of the air ducts:
Maximum length of the air ducts
m
Inner diameter 150 mm
10 m
Inner diameter 160 mm
15 m
Inner diameter 200 mm
25 m
When determining the overall length of the air ducts, the equivalent length of the accessories, e.g.
pipe elbows reduction pieces, etc.
Accessories
Equivalent length in m
Elbow 90° (
Φ
160 mm)
3
Elbow 90° (
Φ
200 mm)
2
Reduction piece
Φ
200x
Φ
160
1
Outer grating (
Φ
160 mm)
2
5.5.3
Connection of Condensate Discharge
The extraction of heat from the air causes the condensation of air humidity in the heat pump.
Depending on the season and hot water requirements, between 1 and 5 litres of condensate per day
accumulate. This condensing water can be used for steam ironing or watering. A discharge tube is
fitted at the back of the device to drain the condensate. If free drainage of the condensation is not
possible, a collecting vessel of at least 10 litres must be provided.
Caution: when connecting condensate outlet care must be taken that the tube is always turned
downwards. If longer tubes are used, a return valve must be fitted at the bottom of the outlet tube to
ensure proper drainage of the condensate and to avoid the discharge odour to spread.