www.austin-hughes.com
UM-IP-ATS-Q318V1 P.11
< 1.7 > SNMP Setup
The intelligent ATS has SNMP ( v1/v2 or v3 ) function which is capable of integration of 3rd party
DCIM to achieve centralized monitoring for power, cooling and environment factors across facilities
and IT systems.
( I ).
Accessing MIB Files
Step 1
. Click the following link to go to the mangement software download page :
http://www.austin-hughes.com/resources/software/infrapower
Step 2
. Select the MIB
fi
le of the intelligent ATS
( II ). Enabling SNMP Support
i.
The following steps summarize how to enable the ATS for SNMP v1 / v2 support.
Step 1.
Connect the ATS to a computer. ( Please refer to < 1.4 > IP con
fi
guration )
Step 2.
Open the Internet Explorer ( I.E. ) version 11.0
Step 3.
Enter the con
fi
gured ATS's address into the I.E. address bar.
Default IP address is “ 192.168.0.1 “
Step 4.
Enter
“ Login name “
&
“ Password “
. Default login name & password are
“ 00000000 “
Step 5.
Select the SNMP from the left navigation pane
Step 6.
The SNMP settings window appears as below :