3. INSTALLATION (CONTINUED)
3.5 Floor protection
!
•
You will require a hearth to protect any combustible floor beneath the
firebox. Your floor protection must extend 30cm beyond the diameter of
the firebox in all directions.
!
•
If installed directly on combustible material, the floor protector must be
made of a 30mm thick sheet of material with a thermal conductivity of a
0.21W/m.K. Non-combustible finishes can be applied to the floor
protector (tiles, steel sheet, light concrete, etc).
!
•
If the combustible floor is installed on concrete, you can replace the
combustible material with a non-combustible material laid directly onto
the concrete.
!
!