14
installation
and
user
manual
pLanninG
2
FLUE
POSITION
FLUE REQUIREMENTS
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE
SERVING ANOTHER APPLIANCE
Aurora Fireplaces must be connected to a chimney
complying with the requirements for Type HT chimneys in
the standard for Chimneys, Factory-built, Residential Type
and Building Heating Appliance, UL 103 / ULC S629. For
example, a class A insulated stainless steel flue chimney
system with a 6-inch minimum inside diameter.
FLUE CONNECTOR REQUIREMENTS
Use the Aurora flue connector to connect into the class
A insulated chimney. This connection must be inside
the insulated body of the ceiling bracket to avoid heat
traps. That a chimney connector shall not pass through
an attic or roof space, closet or similar concealed space,
or a floor, or ceiling. Where passage through a wall,
or partition of combustible construction is desired,
the installation shall conform to CAN/CSA-B365,
Installation code for Solid-Fuel Burning Appliances and
Equipment.
WARNING: The chimney and chimney connector must
be in good condition and be kept clean.