AURATON S08 User Manual Download Page 6

7

6

The display will show for five seconds the blinking symbols indicating the 
controller’s  operation  mode  (

  or 

)  and  then,  for  another 

[CO]

[CU]

5 seconds, the value of the hysteresis setting (e.g. 

).

.

[H4]

Example

When setting hysteresis value of, e.g. H4 in the CO mode and 

temperature of e.g. 40 °C, the pump will be switched on when 
the temperature exceeds 42 °C and will be switched off when 
the temperature drops to 38 °C. 

When  this  information  is  displayed,  you  can  change  the  set  value  by 
pressing the (

) or (

+

) button. The range of hysteresis values that can be 

set for the controller is 

from 2°C to 8°C

 (

 to 

).  After the change is 

[H2]

[H8]

made, it is stored automatically. 

 

The hysteresis can be changed by simultaneously pressing and holding 
both the (

) and the (

+

) button for 4 seconds.

 

When setting hysteresis value of, e.g. H4 in the CU mode and 

temperature of e.g. 40 °C, the pump will be switched off when 
the temperature exceeds 42 °C and will be switched on when 

Setting of the hysteresis

To do so, press and hold the right button (

+

) for 2 seconds. Use of this 

functionality is indicated by illumination of the right red indicator light 
and the 

ON

 (

) characters shown for 10 seconds.

[

ON

]

The controller makes it possible to manually switch on and off  

 

the CH or 

DHW pump.

NOTE: 

In  the 

  mode  of  operation,  the  pump  will  be  on  until  the 

[CU]

temperature reaches 90 °C. Once this value is reached, the pump 
will  switch  off.  After  the  temperature  drops  below  90°C,
the pump is switched on again.

The pump continues to work regardless of the temperature set on the 
controller and the actual temperature in the location of the sensor.
In  order  to  switch  the  pump  off,  press  and  hold  the  right  button  (+2)
for 2 seconds again.

Manual switching on and off 
of the CH or DHW pump

Indication of operation of the pump

Automatic operation

    

Switching  on  of  the  pump  is  indicated  by  the 

of the pump

 

right 

green indicator light blinking

.

Manual operation

  

  

Switching on of the pump is indicated by the of 

the pump

 

right 

red indicator light blinking

.

Disabling the pump alarm

software Version 1.2 and later

The  display  will  show  for  5  seconds  the  blinking  operation  mode  of  the 
controller (CO or CU) and then for another 5 seconds it will show the value of 
hysteresis set (e.g. H4).

To do this, enter the menu of the controller:

When this message is displayed, use buttons (

) or (

+

) to change this value to 

"A 0", which means disabling alarm E 1.

The next setting is for stopping the alarm of E 1 pump; the display will show 
blinking message "A 1" (default setting), which indicates active fire alarm.

In specific situations, it is possible to disable the alarm of disconnected or 
damaged E 1 pump. It can be done in the case of connecting a pump with a low 
power or electronically controlled.

Change the settings by simultaneously pressing and holding buttons (

) and (

+

for 5 seconds.

Summary of Contents for S08

Page 1: ...S08 USER MANUAL EN www auraton pl ...

Page 2: ...ntroller s sensor measures the temperature of the water on the supply side of the CH system In a CH system with a coal fired boiler the controller switches off the circulation pumpaftertheflameintheboilerisextinguished TherangeofsettingsfortheCHpumpsisfrom20 Cto90 C Can be used as a DHW pump controller In domestic hot water DHW systems the controller pump assembly forces circulation of water in DH...

Page 3: ...unding tothe terminal ź After the wires have been secured to prevent accidental pulling connectthepowersupplycabletoa230V 50Hzpoweroutlet Connectingthecontroller NOTE The sensor must not be immersed in liquids or installed at fluegasoutletstothestack Mountingthecontroller ź Connecttheblueconductor zeroconductor tothe N terminal ź The controller must be mounted on a wall or another support using tw...

Page 4: ...h Function button operation modes Temperature sensor Power supply wire Pump control output First s 2 Softw 4 Curre On the l Hold the controll illumina After th isshown Thesen 3 Cont 1 Displ The tem appropr After th thisvalu The tem leftorri Settin Thecha Thecon In order the a showno The ope holding show th isdispla Settin ...

Page 5: ...thenbesetusingthe or button After the setting has been performed the controller automatically stores thisvalueandthedisplayshowsthecurrentsensortemperature The temperature setting function can be activated by briefly pressing the leftorrightbutton Setting the temperature Thechangeoftheoperationmodeissavedautomatically Thecontrollercanbesetinoneoftwooperationmodes In order to check the controller s...

Page 6: ...40 C the pump will be switched off when the temperature exceeds 42 C and will be switched on when Setting of the hysteresis To do so function andthe The con DHWpu NOTE The pum controll In order for2sec Manu of the Indic Automa ofthep Manual thepum Disabling the pump alarm softwareVersion1 2andlater The display will show for 5 seconds the blinking operation mode of the controller CO or CU and then ...

Page 7: ... is reached the pump will switch off After the temperature drops below 90 C thepumpisswitchedonagain The pump continues to work regardless of the temperature set on the controllerandtheactualtemperatureinthelocationofthesensor In order to switch the pump off press and hold the right button 2 for2secondsagain Manual switching on and off of the CH or DHW pump Indication of operation of the pump Auto...

Page 8: ...tched on The pump has been switched off waiting for the power supply to be temporarily disconnected COmode thepumphasbeenswitchedon CUmode the pump has been switched off The output power supply is disconnected waiting for the defect to be repaired once thedefectisrepaired pressanybutton COmode the pump has been switched off CUmode thepumphasbeenswitchedoff waiting for the defect to be repaired rep...

Page 9: ...he controller in the mode CO work with a CH pump CH boiler temperature sensor pump L N yellow green wire blue wire brown wire Switching the controller off In order to switch the controller off press and hold for 2 seconds the button the display is then switched off and the green LED changes its colortored The controller is switched off but the GUARD function continues to be active 230V ched off re...

Page 10: ...on ź Theo solve Dispo 10 Wiring diagram of the controller in the mode CU work with a DHW pump Gas boiler Pump DHW sensor DHW tank 230V Wiring diagram with a DHW tank DHW tank Pump 230V temperature sensor fix it with a band HW hot water CW cold water Wiring diagram of a DHW circuit ...

Page 11: ...vicewithliquidsandmoisture ź Donottouchthedisplaywithsharpobjects ź Theoutsideofthecontrollermustbecleanedwithacleancloth Donotuse solvents suchasbenzene thinners oralcohol Disposal of the device The device is marked with a symbol of a crossed waste bin Pursuant to European Directive 2002 96 EC and to the Act on waste electrical and electronic equipment such mark indicates that the device at the e...