Figure 37: Information in the status bar (top)
[1]
Operation mode
[2]
Error symbol (only for faults and warnings)
[3]
ID number: S = Status page
Navigation support
If further details or information are available with reference to the display, the following
indications
Details
or
More
appear in the navigation support (bottom display row).
Then, further information can be displayed via the push button.
Figure 38: Navigation support (bottom)
[1]
shows list with detailed indications
[2]
shows further available information
The navigation support (bottom row) is faded out after approx. 3 seconds. Press any
push button (selector switch in position 0 (OFF)) to fade in the navigation support.
7.2.1.
Feedback indications from actuator and valve
Display indications depend on the actuator version.
Valve position (S0001)
●
S0001
on the display indicates the valve position in % of the travel.
●
The bar graph display appears after approx. 3 seconds.
●
When issuing an operation command, an arrow indicates the direction
(OPEN/CLOSE).
Figure 39: Valve position and direction of operation
Reaching the preset end positions is additionally indicated via
(CLOSED) and
(OPEN) symbols.
Figure 40: End position CLOSED/OPEN reached
0%
Actuator is in end position CLOSED
100% Actuator is in end position OPEN
Torque (S0002)
●
S0002
on the display indicates the torque applied at the actuator output.
●
The bar graph display appears after approx. 3 seconds.
38
SQEx 05.2 – SQEx 14.2 / SQREx 05.2 – SQREx 14.2 Control unit: electronic (MWG)
Indications
ACExC 01.2 Non-Intrusive Modbus TCP/IP
Summary of Contents for SQEx 05.2