8.
Check whether O-rings [3] are in good condition, replace if damaged.
9.
Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-rings and
insert them correctly.
10. Fit electrical connection (connection frame) and fasten screws [4] (with gaskets)
evenly crosswise.
11. For versions with terminal compartment in type of protection Ex d (flameproof
enclosure): Fasten grub screws [6] (tightening torque approx. 10 Nm).
Information: The flameproof enclosure is only guaranteed provided the grub
screws are fastened [6].
12. Fit cover [1] and fasten screws [2] evenly crosswise.
12.2.2.
Disconnection from the mains with KP/KPH and KES electrical connection
Ignition of potentially explosive atmospheres caused by sparks.
Risk of death or serious injury.
→
Before opening the flameproof enclosure, ensure absence of gas and voltage.
→
Wait for 30 seconds after power cut-off prior to opening the housing.
→
Handle cover and housing parts with care.
→
Joint surfaces must not be damaged or soiled in any way.
→
Do not jam cover during fitting.
Figure 80: KP/KPH and KES electrical connection
[1]
Cover
[2]
Screws for housing
[3]
O-ring
[4]
Plug-in frame (KP/KPH)
[5]
Connection frame (KES)
Removing the plug:
1.
Loosen the screws [2].
2.
Remove electrical connection.
➥
Cover [1] and plug-in type frame [4] or connection frame [5] remain together.
3.
Seal open plug/socket connection, e.g. using AUMA protection cover and
parking frame.
Fitting the plug/socket
connector:
4.
Clean sealing faces of plug/socket connector and housing.
5.
Preserve joint surfaces with an acid-free corrosion protection agent.
79
SAVEx 07.2 – SAVEx16.2/SARVEx 07.2 – SARVEx16.2 Control unit: electronic (MWG)
ACVExC 01.2 Non-Intrusive
Servicing and maintenance