21.7 Positioner adjustment end position CLOSED (inverse operation)
.
Run actuator with push button
(local controls) to
end position
CLOSED.
.
Connect voltmeter to measuring points MP2 and MP1 for measuring the
actual value E2:
When position feedback is set correctly, the voltmeter shows 5 V.
If measured value is not correct:
Adjust position feedback according to clauses 16. and 17. and repeat
“positioner adjustment”.
.
Connect max. command signal (nominal value E1) = 20 mA.
.
Connect voltmeter to measuring points MP4 and MP3 for measuring the
nominal value E1:
For a nominal value of 20 mA, the voltmeter shows 5 V.
If measured value is not 5 V:
Check the externally supplied command signal E1.
42
Multi-turn actuators SA 07.1 – SA 30.1/SAR 07.1 – SAR 30.1
with actuator controls AUMA MATIC AM 01.1/AM 02.1
Operation instructions
If
LED display:
Then
Required setting in end position CLOSED:
the LEDs are not illuminated
Turn potentiometer “max” (P4) slightly counterclockwise until
LED
(V27 yellow) is illuminated
LED
(V27 yellow)
is illuminated
Turn potentiometer “max” (P4) clockwise until LED
(V27 yellow)
is no longer illuminated.
Then turn potentiometer “max” (P4) slightly counterclockwise until
LED
(V27 yellow) is illuminated.
LED
(V28 green)
is illuminated
Turn potentiometer “max” (P4) slightly counterclockwise until the
LED
(V28 green) is no longer illuminated and
LED
(V27 yellow) is illuminated.
Table 11
Figure 52: Positioner board A7 - standard
V28
V27
V18
V10
P10
MP2(+)
MP1(–)
P9 (
Δ
E)
P7 (Sens)
P3 (0)
P4 (max)
S2-7
S3-7
Meas.
points:
Meas. points: MP3(+)/MP4(–) for E1