6.4.
Close terminal compartment
Explosion due to damaged flameproof enclosure!
Risk of death or serious injury!
→
Handle cover and housing parts with care.
→
Joint surfaces must not be damaged or soiled in any way.
→
Do not jam cover during fitting.
Figure 16: Terminal compartment: close
[1]
Cover
[2]
Screws
[3]
O-ring
Short-circuit and electric shock due to pinching of cables!
Risk of death or serious injury!
→
Carefully assemble cover to avoid pinching the cables.
1.
Clean sealing faces of cover [1] and housing.
2.
Check whether O-ring [3] is mounted in the provided groove.
3.
Fit cover [1] and fasten screws [2] evenly crosswise at 24 Nm (M8).
Information: The PE conductor must be correctly connected to the cover
housing. If the cable has been removed from the cover, it must be tightened
applying 2.2 Nm tightening torque prior to re-placing the cover.
6.5.
External earth connection
The actuator is equipped with an earth connection consisting of a metal plate and a
hex. socket cap head screw with shaft bearing race.
22
PF-M25X – PF-M100X
Electrical connection
Parallel