SQ 05.2 – SQ 12.2 / SQEx 05.2 – SQEx 12.2
Switchgear version: Contactors
Safe STOP OPEN or Safe
STOP CLOSE
Safe ESD
Safety function
2.28 x 10
–3
2.20 x 10
–3
PFD
avg
T
Proof
= 1 Jahr (1001)
2.33 x 10
–4
2.06 x 10
–4
PFD
avg
T
Proof
= 1 Jahr (1002)
SIL 2 (HFT = 0)
SIL 3 (HFT = 1)
SIL 2 (HFT = 0)
SIL 3 (HFT = 1)
SIL capability
including detected "annunciation" failures (
λ
AD
) (failures in diagnostic function)
1)
Table 16: SQ .2/SQEx .2 type range with AC 01.2/ACExC 01.2 actuator controls in
SIL version, with heating system
SQ 14.2 / SQEx 14.2
Switchgear version: Contactors
Safe STOP OPEN or Safe
STOP CLOSE
Safe ESD
Safety function
675 FIT
185 FIT
λ
S
180 FIT
945 FIT
λ
DD
1)
310 FIT
264 FIT
λ
DU
73 %
81 %
SFF
36 %
78 %
DC
2.61 x 10
–3
2.63 x 10
–3
PFD
avg
T
Proof
= 1 Jahr (1001)
2.69 x 10
–4
2.51 x 10
–4
PFD
avg
T
Proof
= 1 Jahr (1002)
SIL 2 (HFT = 0)
SIL 3 (HFT = 1)
SIL 2 (HFT = 0)
SIL 3 (HFT = 1)
SIL capability
including detected "annunciation" failures (
λ
AD
) (failures in diagnostic function)
1)
Table 17: SQ .2 series with AC 01.2 controls in SIL version, with heating system
SQ 05.2 – SQ 12.2 / SQR 05.2 – SQR 12.2
Switchgear version: Thyristors
Safe STOP OPEN or Safe
STOP CLOSE
Safe ESD
Safety function
626 FIT
138 FIT
λ
S
181 FIT
938 FIT
λ
DD
1)
218 FIT
223 FIT
λ
DU
78 %
82 %
SFF
45 %
80 %
DC
1.84 x 10
–3
2.28 x 10
–3
PFD
avg
T
Proof
= 1 Jahr (1001)
1.88 x 10
–4
2.14 x 10
–4
PFD
avg
T
Proof
= 1 Jahr (1002)
SIL 2 (HFT = 0)
SIL 3 (HFT = 1)
SIL 2 (HFT = 0)
SIL 3 (HFT = 1)
SIL capability
including detected "annunciation" failures (
λ
AD
) (failures in diagnostic function)
1)
Table 18: SQ .2 series with AC 01.2 controls in SIL version, with heating system
SQ 14.2 / SQR 14
Switchgear version: Thyristors
Safe STOP OPEN or Safe
STOP CLOSE
Safe ESD
Safety function
665 FIT
138 FIT
λ
S
181 FIT
973 FIT
λ
DD
1)
258 FIT
273 FIT
λ
DU
76 %
80 %
SFF
41 %
78 %
DC
43
Part-turn actuators
with AC 01.2-SIL/ACExC 01.2-SIL
Safety-related figures