INSTALLATION
PRIMO PILOT
MANUAL
-
19
Parameter N°
Description
Unit
Range of setting
Factory
setting
P202
Maximum exterior temperature (TEMA)
°C
11
to
25
20
P203
Minimum exterior temperature (TEMI)
°C
-
30
to
10
-
5
P204
Summer/winter changeover: choice of changeover method
-
auto
: changeover is done automatically based on
the exterior temperature
manu
: changeover is done manually by the user
manu
P205
Summer/winter time delay: time period for observation of the exterior
temperature before automatic season changeover. Only used if
automatic changeover is activated.
hour
0
to
48
12
P206
Reactivity: the temperature for heating takes into account the ambient
temperature to accelerate heating time when heating is switched on or
restarted.
-
yes
: reactivity activated
no
: reactivity deactivated
no
P207
Anticipation of heating: heating restarted before return from holidays
(for a home already at the set temperature on return)
-
yes
: anticipation activated
no
: anticipation deactivated
no
P208
Minimum exterior temperature for operation using only the HP (TEPAC).
The back-up is authorised to operate in colder temperatures.
°C
P209
to
20
2
P209
Maximum exterior temperature for operation using only the back-up
(TEAPP).
The heat pump is authorised to operate in warmer temperatures.
°C
-
20
to +
10
-
20
P210
Full-hour operation
-
0
: no operation allowed
1
: HP limited to 1st power stage
2
: HP limited to 2nd power stage
3
: full HP without back-up
4
: do not use
5
: do not use
6
: full autorization : HP + back-up
7
: back-up without HP
8
: anti-frost confort level
9
: eco
10
: do not use
6
P212
Type of back-up
-
no
: no backup
Elec
: Electrical back-up
no
P213
Heat pump time-out: allows the heat pump to continue running for a
period of time after intervention of the back-up
min.
1
to
20
5
P214
Diff erence in temperature between the back-up and the heat pump
°K
0
to
7
P212 = ELEC
4
P215
Presence of a heat pump
-
0
: operation without a heat pump
1
: presence of a heat pump
1
P216
to
p227
Not concerned
-
Do not change the setting
0.5
P228
Post-circulation of the heat pump circulator pump
-
Do not change the setting
3
P229
Not concerned
-
Do not change the setting
0.5
P230
Speed of heating circuit circulator pump
%
10
to
100
100
P231
Set temperature of heating water
°C
auto
: automatic set temperature from the air
sensor or exterior sensor (if connected)
or
20
to
70
: setting fi xed in °C
AUTO
P232
Maximum set temperature (TCMA) for the heating circuit
°C
P233
to
70
70
6.4 - List of parameters which can be set