SPECIFICATIONS
O
Outputs
Outputs on power interface board
Main contactor (13, 14) ............................................................................................................................................................. Normally Open
Bypass contactor (23, 24) ......................................................................................................................................................... Normally Open
Run Output/ PFC (33, 34) ....................................................................................................................................................... Normally Open
Fan control output (43, 44) ..................................................................................................................................................... Normally Open
Outputs on Controller
Output Relay A (43, 44) ........................................................................................................................................................... Normally Open
Output Relay B (51, 52, 54) ............................................................................................................................................................ Changeover
Output Relay C (61, 62, 64) ........................................................................................................................................................... Changeover
Analog output (B10, B11) ............................................................................................................................................ 0-20 mA or 4-20 mA
Characteristics
.............................................................................................................................................................................................. 10 A @ 250 VAC resistive
............................................................................................................................................................................................. 6 A @ 250 VAC 15 p.f. 0.3
................................................................................................................................................................................................. 10 A @ 30 VDC resistive
Environmental
Degree of Protection
Power Assembly ...................................................................................................................................................................................................... IP00
Controller ........................................................................................................................................................................................... IP54/ NEMA 12
Operating temperature ....................................................................................................... -
Ý&WR&ZLWKGHUDWLQJWR&
Humidity ................................................................................................................................................................ 5% to 95% Relative Humidity
Storage temperature ....................................................................................................................................................................... -
Ý&WRÝ&
Humidity ................................................................................................................................................................ 5% to 95% Relative Humidity
Operating Altitude ............................................................................................................................ 0 - 1000 m, above 1000 m with derating
Pollution degree ................................................................................................................................................................................. Pollution Degree 3
Vibration ....................................................................................................................................................................................... Designed to IEC 60068
EMC Emission
Equipment class (EMC) ........................................................................................................................................................................................... Class A
Conducted radio frequency emission ......................................................................................... 10 kHz to 150 kHz: < 120 - 69 dB
μ
V
........................................................................................................................................................................... 0.15 MHz to 0.5 MHz: < 79 dB
μ
V
............................................................................................................................................................................... 0.5 MHz to 30 MHz: < 73 dB
μ
V
Radiated radio frequency emission ......................................................................................... 0.15 MHz to 30 MHz: < 80-50 dB
μ
V/m
................................................................................................................................................................ 30 MHz to 100 MHz: < 60-54 dB
μ
V/m
.................................................................................................................................................................. 100 MHz to 2000 MHz: < 54 dB
μ
V/m
This product has been designed as Class A equipment. Use of this product in domestic environments may cause
radio interference, in which case the user may be required to employ additional mitigation methods.
EMC Immunity
Electrostatic Discharge ................................................................................................................. 6 kV contact discharge, 8 kV air discharge
Radio Frequency Electromagnetic Field ...................................................................................................... 80 MHz to 1000 MHz: 10 V/m
Fast Transients 5/50 ns (main and control circuits) ....................................................................... 2 kV line to earth, 1 kV line to line
Surges 1.2/50
μ
s (main and control circuits) ................................................................................... 2 kV line to earth, 1 kV line to line
Voltage dip and short time interruption (safe shutdown) .......................................................... 5000 ms (at 0% nominal voltage)
Standards Approvals
C
....................................................................................................................................................................................................... EMC requirements
CE ......................................................................................................................................................................................................... EMC EU Directive
1
Short circuit current, with appropriate R rated fuses fitted.
2
It is critical that the circuit breaker and associated protection relay are set to trip <150 ms. Failure to do so could
result in SCR rupture and subsequent arc fault.
3
Excludes contactors and/or circuit breakers.
12