INSTRUCTIONS
1.
Important User Information
Observe all necessary safety precautions when controlling the soft starter remotely.
Alert personnel that machinery may start without warning.
It is the installer's responsibility to follow all instructions in this manual and to follow
correct electrical practice.
Use all internationally recognised standard practice for RS-485 communications when
installing and using this equipment.
2.
Installation
2.1
Installation Procedure
1.
Push a small flat-bladed screwdriver into the slot in the centre of the expansion
port cover, and ease the cover away from the starter.
2.
Line up the card with the expansion port. Gently push the card along the guide rails
until it clicks into the starter.
B4 B5 1011 12 13 14 15 21 22
33 34 41 42 44 53 54
B4 B5 1011 12 13 14 15 21 22
33 34 41 42 44 53 54
1
2
17049.
A
2.2
Connecting to the Network
After the card is in place, control power can be restored and field wiring can be
connected via the 5-way connector plug.
3
5
4
2
1
17846.
A
Pin
Function
1, 2
Data A
3
Common
4, 5
Data B
2
Modbus RTU Card (710-16499-00B)