INSTRUCTIONS
Upload single parameter to starter
Write Parameter 16 (2I
Stop Mode
), set = 1
Message Starter Address Function Code
Register
Data
CRC
In
20
06
40024
1
CRC1, CRC2
Out
20
06
40024
1
CRC1, CRC2
Upload multiple parameters to starter
Write Parameters 9, 10, 11 (parameters 2B
Start Ramp Time
, 2C
Initial Current
, 2D
Current Limit
). Set to values of 15 seconds, 300%, 350% respectively.
Message Starter Address Function Code
Register
Data
CRC
In
20
16
40017,3
15, 300, 350 CRC1, CRC2
Out
20
16
40017,3
15, 300, 350 CRC1, CRC2
NOTE
This function can only be used to upload consecutive parameters. The
Register field indicates the number of parameters to be uploaded, and the
register number of the first parameter.
4.8
Trip Codes
Trip
Code
Description
0
No trip
1
Excess start time
2
Motor overload
3
Motor thermistor
4
Current imbalance
5
Frequency
6
Phase sequence
7
Instantaneous overcurrent
8
Power loss
9
Undercurrent
10
Heatsink overtemperature
11
Motor connection
12
Input A trip
13
FLC too high
14
Unsupported option (function not available in inside delta)
15
Communications card fault
16
Forced network trip
17
Internal fault
18
Overvoltage
19
Undervoltage
23
Parameter out of range
Modbus RTU Card (710-16499-00B)
13