background image

         AUBER INSTRUMENTS

  

 

 

 

 

 

 

 

         

WWW.AUBERINS.COM  

 

 

         2017.10                                                                     

   

                                                       P2/3 

 

Table 1. Parameters Description 

Code

 

Description 

Setting Range 

Initial  Note 

Menu for set point (Figure 2) 

tSP 

tSP 

Temp. Set Point 

-40~176 ºF 

-40~80 ºC 

75.0 

HSP 

HSP 

Humidity Set Point 

0~99.9 %RH 

40.0 

Menu for parameters (Figure 3) 

Edt 

EDT 

Menu Selection 

tE: Temp. Menu 

Hu: Humidity Menu 

SYS*: System 

Menu 

TE 

Temp. control settings (Edt = tE) 

C-F 

C-F 

Temp. Unit 

C: Celsius 

F: Fahrenheit 

 

tCM 

tCM 

Temp. Control Mode 

Ht: Heating Control 

CL: Cooling 

Control 

CL 

 

TdF 

TDF 

Temp. Control 

Differential 

0~50.0 

3.0 

toF 

toF 

Temp. Calibration 

Offset 

-10.0~10.0 

tAH 

TAH 

Temp. High  

Limit Alarm 

-40~176 ºF 

-40~80 ºC 

95.0 

tAL 

TAL 

Temp. Low  

Limit Alarm 

-40~176 ºF 

-40~80 ºC 

32.0 

TAS 

TAS 

Temp. Anti-short 

Cycle Delay (only for 

cooling) 

0~12 min 

TSF 

TSF 

Temp. Sensor 

Failure Operation 

ON: Output 

energized 

OFF: Output de-

energized 

OFF 

Humidity control settings (Edt = Hu) 

HCM 

HCM 

Humidity Control 

Mode 

deH: 

Dehumidifying 

H: Humidifying 

 

HdF 

HDF 

Humidity Control 

Differential 

0~50.0 

3.0 

HoF 

HoF 

Humidity Calibration 

Offset 

-10.0~10.0 

HAH 

HAH 

Humidity High Limit 

Alarm 

0~99.9 

90.0 

HAL 

HAL 

Humidity Low Limit 

Alarm 

0~99.9 

10.0 

HAS 

HAS 

Humidity Anti-short 

Cycle Delay (only for 

dehumidifying) 

0~12 min 

HSF 

oFF 

Humidity Sensor 

Failure  

operation 

ON: Output 

energized 

OFF: Output de-

energized 

OFF 

System setting (Edt = SYS*) 

PSD 

PSD 

Device Access 

Password 

100 ~ 999 

666 

 

SET

T

RH

 tSp

 5 4

.

2

T

RH

 1 5

.

0

 HSp

RH

T

 6 8

.

9

 3 6

.

8

SET

Humidity Set Point

Temp. Set Point

SET

 

Figure 2. Flow Chart Part 1 

 6 8

.

9

 3 6

.

8

3 sec

T

RH

 Edt

 tE

T

RH

 Edt

 Hu

T

RH

 C-F

 F

T

RH

HcM

 deH

T

RH

Dn
Up

 6 8

.

9

 3 6

.

8

T

RH

SET

SET

SET

SET

Temp.
Unit

Humidity
Control 
Settings

Humidity 
Control 
Mode

Temp.

Control

Settings

 Edt

sys

T

RH

Dn
Up

SET

System

Setting*

psd

666

T

RH

Access*

Password

SET

SET

 

 

Figure 3. Flow Chart Part 2 

 
Note 1.

 For heating (or humidifying), the output will be off when the 

temperature (or humidity) reaches the set point; it will be on again when the 
temperature (or humidity) drops down to tSP - tdF (or HSP - HdF). 
 
For cooling (or dehumidifying), the output will be off when the temperature (or 
humidity) reaches the set point; it will be on again when the temperature (or 
humidity) rises to tSP + tdF (or HSP + HdF). 
 
Small differential gives tight control. Large differential reduces the frequency of 
cycle on and off, and it will extend the life of relay and compressor. 

 

Note 2.

 The offset is used to set an input offset to compensate the error 

produced by the sensor or input signal itself. 
 
For example, for temperature reading, if the unit displays 37 ºF when the actual 
temperature is 32ºF, setting parameter toF = - 5 will make the controller display 
32ºF. 
 

Note 3.

 The low limit alarm will be always lower than the high limit alarm. When 

the measured temperature (humidity) is higher than tAH (HAH), the 
temperature (humidity) high limit alarm will be on; when the measured 
temperature (humidity) is lower than tAL (HAL), the temperature (humidity) low 
limit alarm will be on. 
 
When alarm is on, the display will be flashing between the measured value and 
alarm type. To mute the alarm when it is on, press the Down key momentarily. 
When the alarm is muted, the alarm indicator (see Figure 1, the small dot on 
the last digit) will be on. If the measured value gets out of the alarm zone then 

Reviews: