background image

         AUBER INSTRUMENTS

  

 

 

 

 

 

 

 

         

WWW.AUBERINS.COM  

 

 

         2020.06                                                                   

   

                                                       P4/10 

 

filt

20

FILT

PV input filter

SET

PV

SV

2S

SET

SET

SET

SET

SET

SET

SET

AL1

Alarm 1

pb

0

Pb

Input Offset

p

0

P

Proportional constant

i

500

I

Integral time

d

100

d

Derivative time

t

10

t

Cycle time

SET

SET

SET

SET

SET

SET

dp

1

dP

Decimal  point position

outh

200

OutH

Output high limit

outl

0

OutL

Output low limit

addr

1

Addr

Communication address

baud

0

Baud

Communication baud

SET

SET

SET

SET

SET

SET

SET

SET

lock

0

Lock

Configuration Privilege

sn

k

Sn

Input Sensor Type

Op-a

1

Reserved

cf

c

CF

Display Temp Unit

alp

1

ALP

Alarm output definition

cool

0

Cool

System Function Selection

puh

1300

PuH

Display High Limit

pul

0

PuL

Display Low Limit

hy

0

.

5

Hy

Hysteresis Band

at

0

At

Auto Tuning

SET

SET

al1

200

al2

10

AL2

Alarm 2

 

Figure 4. Flow chart for system parameter menu 

 
 

5.3.1.

 

Alarm function & parameters  

This controller has two alarm output relays: AL1 relay (terminal 1 & 2) and AL2 
relay (terminal 13 & 14). AL1 relay is temperature alarm. AL2 relay is program 
ending alarm.  
 
This controller has three alarm parameters: AL1, AL2, ALP.  
 
Parameter  AL1:  Temperature  alarm  value  for  AL1  relay.  See  ALP  definition 
below. 
 
Parameter AL2: Duration time for program ending alarm. Unit is per seconds. 
Available range is 0s to 200s. AL2 is set as 10s, it means once the ramp soak 
program is completed, AL2 relay will be triggered continuously for 10s. Then it 
will be dropped off.  
 
ALP: Alarm output definition for AL1 relay. The temperature difference to release 
the triggered alarm is 0.5° F (parameter CF = 1) or 0.5° C (parameter CF = 0). 
 
 
 

Table 3. ALP Definition 

ALP 
Value 

Alarm Type 

Alarm ON 
Condition 

Alarm OFF 

Condition 

AL1 is disabled 

 

 

Absolute high 
alarm 

PV > AL1 

PV < AL1 

 0.5 

Absolute low 
alarm 

PV < AL1 

PV > AL1 + 0.5 

Derivation high 
alarm 

PV > SP + AL1 

PV < SP + AL1 

 0.5 

Derivation low 
alarm 

PV < SP 

 AL1 

PV > SP 

 AL1 + 0.5 

Band alarm, 
direct acting (out 
of range alarm) 

PV < SP 

 AL1 or 

PV > SP + AL1 

PV > SP 

 AL1 + 0.5 

and 

PV < SP + AL1 -0.5 

Band alarm, 
reverse acting (in 
range alarm) 

PV > SP 

 AL1 

and  

PV < SP + AL1 

PV < SP 

 AL1 

 0.5 

or 

PV > SP + AL1 + 0.5 

 
Legend:  
PV: current reading temperature 
AL1: Value of parameter AL1 
SP: Set temperature in current step (SV). 
 

5.3.2.

 

Input offset “Pb”

 

Input offset Pb is used to add an offset value to compensate the sensor error or 
simply to shift the reading. For example, if the controller displays 2ºC when probe 
is in ice/water mixture, setting Pb = -2, will make the shift the temperature reading 
to 0ºC. 
 

5.3.3.

 

Control mode 

1) PID control mode 

Please note that because this controller uses fuzzy logic enhanced PID control 
algorithm, the definition of the control constants (P, I and d) are different than 
that of the traditional proportional, integral, and derivative parameters.  
 
(1) 

Proportional constant “P”

 

Please note that the P constant is not defined as Proportional Band as in the 
traditional model. Its unit is not in degrees. A larger constant results in larger and 
quicker action, which is the opposite of the traditional proportional band value. It 
also functions in the entire control range rather than a limited band. 
 

(2) Integral time “I”

 

Integral action is used to eliminate offset. Larger values lead to slower action. 
Increase  the  integral  time  when  temperature  fluctuates  regularly  (system 
oscillating).  Decrease  it  if  the  controller  is  taking  too  long  to  eliminate  the 
temperature offset. When I = 0, the system becomes a PD controller. 
 

(3) Derivative time “D”

 

Derivative  action  can  be  used  to  minimize  the  temperature  overshoot  by 
responding to its rate of change. The larger the number, the faster the action. 
 

2) On/off control mode  

It is necessary for inductive loads such as motors, compressors, or solenoid 

valves that do not like to take pulsed power. It works like a mechanical thermostat. 
When  the  temperature  passes  hysteresis  band  (Hy,  see  section  5.3.6),  the 
heater (or cooler) will be turned off. When the temperature drops back to below 
the hysteresis band, the heater will turn on again. 

 

To use the on/off mode, set

 P = 0

. Then, set Hy to the desired range based on 

control precision requirements. Smaller Hy values result in tighter temperature 
control, but also cause the on/off action to occur more frequently. 

Summary of Contents for SYL-5342P-S

Page 1: ...FILt 0 Display resolution 1 C 1 F or 0 1 C 0 1 F Control mode Fuzzy logic enhanced PID control On off control Output mode Relay contact NO 250VAC 7A 120V 10A 24VDC 10A Alarm relay rating Relay contact...

Page 2: ...stall The relay outputs AL1 and AL2 are dry single pole switches They do not provide power by themselves Please see Figure 7 and 8 for how they are wired when 120V power is supplied The wiring diagram...

Page 3: ...e is 1 or 2 press SET and hold for roughly 2 seconds until the parameter setup menu is displayed display mode 3 Please refer to 5 3 for how to set the parameters 5 2 Setup flow chart While in the para...

Page 4: ...cting in range alarm PV SP AL1 and PV SP AL1 PV SP AL1 0 5 or PV SP AL1 0 5 Legend PV current reading temperature AL1 Value of parameter AL1 SP Set temperature in current step SV 5 3 2 Input offset Pb...

Page 5: ...20 seconds To drive external relay or contactor output it should be set longer to prevent contacts from wearing out too soon Normally 20 40 seconds 5 3 5 Input digital filter FILt If measurement input...

Page 6: ...point This mode is suitable for the applications in which power failure does not affect production PdE 3 After power is turned on this controller will jump to the beginning of the program step 1 and r...

Page 7: ...if this controller is locked Please see section 5 3 9 for the details of LOCK parameter Even the controller is under single step mode RUN 0 user can still get access to all the ramp soak settings tho...

Page 8: ...the controller will run from step 1 automatically 6 2 11 Check the Step Number and Jump the Program To check at which step the program is running press the SET key once The upper window will show StEP...

Page 9: ...ature The temperature set point of the last step will linearly ramp to the set point of the current step over the ramp time of current step Then the set point of current step will be held over the soa...

Page 10: ...igure 12 Temperature profile and relay AL1 AL2 actions in the example program 8 3 Example 3 powder coating oven A powder coating oven needs to heat up to 375 F at its maximum speed Then hold the tempe...

Reviews: