background image

 

 AUBER INSTRUMENTS

    

 

 

 

 

 

 

            

WWW.AUBERINS.COM 

 

2021.01             

 

 

               P4/6 

and used for the system. Please note that auto-tuning is only for PID control 
mode. There is no need for auto-tune when using ON/OFF mode (when P = 0).  
To stop the auto-tuning, enter the parameter setting mode, set At = OFF. Then, 
the previous PID parameters values are resumed. 
 

AT start

AT calculation

AT end

ON

OFF

ON

OFF

ON/OFF

PID 

Figure 5. Auto tuning

SV

PV

 

 

Hy2

1

.

0

Figure 4. System setup flow chart.

SET 3S

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

AL1

999

.

9

ALP 1
Alarm 1 Definition

ALP 2
Alarm 2 Definition

Cool
Cooling Control

OUTH
Output High Limit

Lock
Configuration Privilege

Sn
Input Type

OPA
Output Mode

CF
Display Unit

DIH
Input High Limit

DIL
Input Low Limit

SC

0

.

0

P

15

.

0

I

240

D

30

AT

OFF

t

10

Hy1

1

.

0

DP

1

ALP2

0

COOL

OFF

Hy

1

.

0

AL2

0

SET

SET

SET

outh

100

LOCK

0

ALP1

0

85

.

5

10

AL1
Alarm1 Setting

AL2
Alarm2 Setting

SC
Input Offset

P
Proportional Constant

I
Integral Time

D
Derivative Time

At
Auto Tune

T
Cycle Time

Hy
Hysteresis Band

Hy 1
Alarm 1 Hysteresis Band

Hy 2
Alarm 2 Hysteresis Band

dP
Decimal Point Position

Sn

k

OPA

0

Dil

0

dih

999

.

9

cf

c

Time

SET

SET

SET

SET

SET

PV

 

4.3 Control action explanations 

4.3.1 PID 

The values of the P, I, and D parameters are critical for good response time, 
accuracy and stability of the system. Using the Auto-Tune function to 
automatically determine these parameters is recommended for the first time 
user. If the auto tuning result is not satisfactory, you can manually fine-tune the 
PID constants for improved performance.  

Proportional Constant (P):

 P is also called the proportional band. Its unit is 

the degree of temperature. For example, P = 50 means the proportional band 
is 50 degrees. Assuming the set temperature SV = 200. When integral, I, and 
derivative, d, actions are removed - the controller output power will change 
from 100% to 0% when temperature increases from 150 to 200 ° C. The 
smaller the P value is, the stronger action will be for the same temperature 
difference between SV and PV. 

Please note: for on/off control mode, P is 

set to 0.

  

 

Integral time (I):

 Brings the system up to the set value by adding to the output 

that is proportional to how far the process value (PV) is from the set value (SV) 
and how long it has been there. When I decreases, the response speed is 
faster but the system is less stable. When I increases, the response speed is 
slower, but the system is more stable. When I = 0, the integration is turned off. 
It becomes to a PD controller that is useful for very slow system.  
 

Derivative time (d):

 Responds to the rate of PV change, so that the controller 

can compensate in advance before |SV-PV| gets too big. A larger number 
increases its action. Setting d-value too small or too large would decrease 
system stability, causing oscillation or even non-convergence. Normally, d is 
set to ¼  of the I value. However, when the controller is in on/off mode (P = 0) 
and cooling control is turned on, d means Delay Timer of the Anti-Short Cycle 
Delay (Asd) function. The delay time ranges from 1-200 minutes. (See 4.3.3 
for details). 
 

4.3.2 On/off control mode  

It is necessary for inductive loads such as motors, compressors, or solenoid 
valves that do not like to take pulsed power. It works like a mechanical 
thermostat. When the temperature passes the SV+Hy, the heater will turn off. 
When the temperature drops back to SV-Hy, the heater will turn on again. (In 
cooling mode, the cooler turns on when temperature passes SV+Hy, and turns 
off when temperature drops back to SV-Hy). 

To use the on/off mode, set P = 

0 and Hy to the desired band.

 Then I and D parameters are not used when 

controller is in heating mode. It can be left at any value. In the cooling mode, 
the D value is used for Anti-Short Delay time. Its value is in minutes (See 4.3.3 
for details).  
 

4.3.3 Cooling control 

When controller is used for cooling control and load is a compressor, it should 
not turn on the compressor when its refrigerant is at high pressure (just after 
turned off). Otherwise, the compressor can be damaged in short time. Two 
methods are commonly used to prevent the rapid cycling of the compressor. 
One is to use on/off control mode (instead of the PID control mode) with wide 
enough hysteresis band, and long cycle rate. The other is to use the Anti-Short 
Cycle Delay (ASd) function. ASd establishes the minimum time that the N.O. 
contacts remain open (after reaching cutout) before closing again. The delay 
overrides any Load Demand and does not allow the N.O. contacts to close until 
the set time-delay value has elapsed. ASd gives time to release the refrigerant 
pressure through evaporator. This controller allows the user to use both 
methods to protect the compressor. You should set the P = 0 for on/off mode. 
Hy should not be less than 2 degrees unless you really need a tight control. The 
cycle rate should be set for 20 second or longer. The D is typically set to 4- 6 
(minutes). 
 

4.3.4 Manual mode 

Manual mode allows the user to control the output as a percentage of the total 
heater power. It is like a dial on a stove. The output is independent of the 
temperature sensor reading. One application example is controlling the strength 
of boiling during beer brewing. You can use the manual mode to control the 
boiling so that it will not boil over to make a mess. The manual mode can be 
switched from PID mode but not from on/off mode. This controller offers a 

bumpless

 switch from the PID to manual mode. If the controller outputs 75% 

of power at PID mode, the controller will stay at 75% when it is switched to the 
manual mode, until it is adjusted manually. See Figure 3 for how to switch the 
display mode. 

To activate the manual control

, pressing the 

 key for 3 

seconds or until the bottom display shows H at the most left digit. The H 
indicating the controller is in manual mode. The number at the right is the 
percentage of output. Press the 

or 

key to adjust the power. To switch back 

to PID mode, pressing the 

 key for 3 seconds or until the H disappeared.  

Reviews: