background image

 

 AUBER INSTRUMENTS

    

 

 

 

 

 

 

            

WWW.AUBERINS.COM 

 

2021.01             

 

 

               P3/6 

Display mode 4: Manual mode.  

Press the 

 key for 3 seconds to enter the manual  mode. In  this mode, the 

lower  display  has  an  H  on  the  most  left.  The  number  on  the  right  is  the 
percentage of power output. Press the 

or 

 to adjust the power. Press the 

 key for 3 seconds again to exit this mode. For more details, please see 4.3. 

Display mode 5: Temperature control parameter setting.

  

Press  the  SET  key  for  3  seconds  to  enter  the  temperature  control  parameter 
setting  mode.  The  upper  display  window  shows  the  parameter  symbol  to  be 
changed, the lower display shows its value. Press 

or 

 to change the 

setting. Then, press SET to go to next parameter. If no key is pressed for 10 
seconds, the display will return to mode 1 automatically. The change of value 
will take effect without the need for pressing the SET key. Figure 4 shows the 
flow chart of the parameters.  
Note:  If  the  controller  is  locked  (see  4.13),  only  limited  parameters  (or  no 
parameters) can be changed. 
 

4.2 Parameter Name, Range and Initial Setting 

 
See Table 2 and Figure 4 for parameter table and flow chart.  
 

4.2.1 Alarm parameters 

This controller has two alarm outputs: Alarm 1 (AL1, NO relay) and Alarm 2 
(AL2, NO relay). Two red alarm indicators are located on the front panel: AL1 
and AL2. Alarm 1 and AL1 indicator are synchronized. Alarm 2 and AL2 
indicator are synchronized. When the AL1 (AL2) indicator is ON, alarm 1 (alarm 
2) relay pulls in. When the AL1 (AL2) indicator is OFF, alarm 1 (alarm 2) relay 
drops off.   
 
Each alarm is set by three parameters: ALP, AL and Hy. ALP1, AL1 and Hy1 
are for Alarm 1. ALP2, AL2 and Hy2 are for Alarm 2. Alarm 1 can be set as 
either temperature alarm (ALP1 = 1 ~ 4) or timer alarm/output (ALP1 = 0). 
Alarm 2 can only be used for temperature alarm (ALP2 = 1 ~ 4). See ALP 
definition below.   

 

 

ALP

 defines the type of alarm.  

ALP = 0, timer alarm/output (alarm 1 only) 
ALP = 1, high limit temperature alarm.  
ALP = 2; low limit temperature alarm.  
ALP = 3; deviation high temperature alarm.  
ALP = 4, deviation low temperature alarm. 
 
Note: When ALP1 is set to 0 (for timer output), parameter AL1 and Hy1 are not 
in use. Only ALP1 can be set to 0. ALP2 = 0 is not functional for SWA-2441B.    
 

AL

 is for the alarm temperature setting. When alarm is set for high/low limit 

alarm, its value is the temperature that alarm will turn on. When alarm is set for 
high/low deviation alarm, its value indicates that the alarm will turn on when 
temperature is deviated AL degree from the set temperature (SV). Note: when 
alarm is set to deviation alarm (ALP1 / ALP2 is set to either 3 or 4), AL1 / AL2 
can only be set to 100 as maximum. 
 

Hy

 is the hysteresis band of temperature alarm. In heating mode, for high limit 

or deviation high alarm mode, the alarm will turn off when the temperature is Hy 
degree below alarm on setting; for low limit and deviation low alarm mode, the 
alarm will turn off when temperature is Hy degree above the alarm on setting.  
 
Example 1: ALP1 = 1 (high limit alarm), AL1 = 250, and Hy1 = 5. In this case, 
alarm 1 will turn on when temperature goes above 250 degrees (AL1) and turn 
off when temperature drop to 245 degrees (AL1-Hy1). 
 
Example 2: SV = 200, ALP1 = 4 (deviation low alarm), AL1 = 10, and Hy1 = 5. 
In this case, alarm 1 will turn on when temperature drop to 190(SV-AL1) and 
turn off when temperature goes up to 195 (SV-AL1+Hy1). 
 

4.2.2 Hysteresis Band “Hy” 

 

The Hysteresis Band parameter Hy is also referred as Dead Band, or 
Differential. It permits protection of the on/off control from high switching 
frequency caused by process input fluctuation. Hysteresis Band parameter is 
used for on/off control, as well as the on/off control at auto tuning. For example: 
When controller is set for on/off heating control mode, the output will turn off 
when temperature goes above SV+ Hy and on again when it drops to below 
SV-Hy. 
 
Table 2. System parameters. 

Mode 2: Press 

 key for 3 seconds then release 

Code 

Sign 

Description 

Setting Range 

Initial 

Setting  Remark 

Sp 

SP 

Set Value 

Decided by DIL, DIH 

100 

 

Mode 5: Press SET key for 3 seconds then release 

AL1 

AL1 

Alarm 1 setting 

-

1999 ~ +9999 ˚C or ˚F

 

999.9 

4.2.1 

AL2 

AL2 

Alarm 2 setting 

-

1999 ~ +9999 ˚C or ˚F

 

0.0 

SC 

SC 

Input offset 

-20 ~ 20 

0.0 

4.10 

Proportional Constant 

0.1 ~ 200.0 

15.0 

4.3.1 

Integral time 

0 ~ 2000 

240 

Derivative time / delay 

time 

0 ~ 200 

30 

At 

At 

Auto-tune 

On/off 

Off 

4.2.3 

Cycle time 

2 ~ 120 

10 

4.4 

Hy 

Hy 

Hysteresis band 

0.1 ~100.0 

1.0 

4.2.2 

Hy1 

Hy1 

Alarm 1 hysteresis 

band 

0.1 ~100.0 

1.0 

4.2.1 

Hy2 

Hy2 

Alarm 2 hysteresis 

band 

0.1 ~100.0 

1.0 

dP 

dP 

Decimal point position 

0 or 1 

4.6 

ALP1 

ALP1 

Alarm 1 definition 

0 ~ 4 

4.2.1 

ALP2 

ALP2 

Alarm 2 definition 

0 ~ 4 

CooL 

COOL 

Cooling control 

On/Off 

Off 

4.10 

outh 

outH 

Output high limit 

0 ~ 100% 

100 

4.12 

Lock 

Lock  Configuration privilege 

0 ~ 50 

4.13 

Sn 

Sn 

Input type 

See Table 3 

4.5 

OPA 

OPA 

Output Mode 

4.9 

dIL 

DIL 

Input low limit 

-1999 ~ DIH 

0.0 

4.7 

dIH 

DIH 

Input high limit 

dIL ~ 9999 

999.9 

CF 

CF 

Display unit 

C, F 

4.11 

Mode 3: Press 

 

key for 3 seconds and release 

tE1 

TE1 

Timer 1 

0 ~ 9999 

10 

4.14 

Te2 

TE2 

Timer 2 

0 ~ 9999 

UPT 

UPT 

Timer unit and timer 

mode 

0 ~ 3 

4.15 

INT 

INT 

Timer control mode 

0 ~ 8 

4.16 

 

4.2.3 At (Auto-tuning) 

The auto-tuning function (also called self-tuning) can automatically optimize the 
PID parameters for the system. The auto-tuning function will use the on/off 
mode to heat up the system until it passes the set point. Then let it cool down. It 
will repeat this about three times. Based on the response time of the system, 
the built-in artificial intelligence program will calculate and set the PID 
parameters for the controller. If your system has a very slow response, the auto 
tuning could take a long time. 
 
To activate auto-tuning, enter the parameter setting mode, set At = ON. The 

“AT” LED on the left lower corner of the controller will light up. Auto

-tune will 

finish when the AT LED turns off. The newly calculated PID parameters are set 

Reviews: