background image

2.2 

Connect  the  incoming  line  to  the  AT87 

module,  using  either  the  grey/green  terminal 
blocks 

(see  section  2.3)

  or  the  3.5mm  socket  (PS 

models  only).  Run  cable  from  the  AT87  module, 
using  either  orange/green  terminal  blocks  or 
male  3.5mm  plug  to  the  equipment  meant  to  be 
protected. 

See 

Wiring 

Guide 

for 

more 

information. 

Adhering to these instructions 
guarantees maximum performance of 
this Protection Device.
 

 

 

IMPORTANT SAFETY 
INSTRUCTIONS CAUTION: 

1.  Never install CCTV wiring during 

a lightning storm. 

2.  This product is intended for 

INDOOR USE ONLY. 

3. 

Risk of Electric Shock - Protector 
is not to be used if physically 

damaged.

 

1. INSTALLATION 

1.1 

Rea d 

an d 

underst and 

a ll 

instructions. 

1.2 

The  1-in-1  AT87  modules  can  be 

installed individually, grounding the unit 

using the ground stud on the underside of 

the  mounting  plate.  Multiple  AT87  modules 

can  also  be  installed  on  2-in-1  and  3-in-1 

mounting  plates,  all  sharing  a  common 

ground  through  the  grounding  stud, 

suitable  for  surface  mount  installations.  In 

planning  an  installation,  location  of  the 

AT87 unit in close proximity to the correct 

ground  point  is  essential  for  protection 

performance.  The  correct  ground  point  is 

defined  as  the  ground  reference  used  by 

the  system  to  be  protected.  In  most 

applications,  this  is  AC  power  ground. 

MINIMIZE the distance  between the AT87 

unit  and  the  identified  ground  point  as 

much as possible. 

2. STAND-ALONE POWER MODULE 

INSTALLATION 

2.1 

To  install  1-in-1  AT87  12V  24V  or 

120V modules as stand-alone units, attach 

a  minimum  #14  AWG  ground  wire  with 

the  supplied  nut,  washer,  and  ring 

terminal  to  the  ground  stud  on  the 

underside  of  the  mounting  plate 

(see 

figure 1). 

The metallic ground stud is the 

unit’s Earth connection. 

2.3 

AT87  MODULES  WITH  CAGE  CLAMP 

TERMINALS: 

The cage clamp mechanism used on 

these  modules  offers  THE  MOST  SECURE  wire 
connection  available.  The  quality  of  connection  is 
significantly 

better 

than 

standard 

screw 

terminals. 

GROUNDING 

The  mounting  plate  must  be  connected  to 
the  ground  reference  used  by  the  system 
being 

protected. 

In 

headend 

environment,  this  grounding  point  may 
be the ground bar in the AC power panel. 
Ground  leads  longer  than  12”  are  not 
suggested. 

INDEPENDENT GROUNDS 

Surge  protection  devices  must  not  be 
connected 

to 

independently 

derived 

grounds. 

WARNING 

The grounding lead must be as short as is 
practically  possible.  Minimize  length  to 
the  inch.  The  ground  wire  should  be  a 
minimum  #14  AWG  for  single-module 
installations  and  #10  AWG  for  multi-
module installations. 

4. WIRING GUIDE 

4.1 

ALL MODULES: 

Ensure  all  modules  are  oriented  with 
protected  ends  toward  the  equipment  and 
unprotected  ends  towards  the  incoming 
line. 

See ground wire installation instructions 

in section 2.1 for 1-in-1 models and 3.1 for 
2-in-1 and 3-in-1 models.

 

4.2 

POWER MODULES: 

AT87  power    protection  modules  use 
colored  terminal  blocks  to  determine 
ground  and  protected/unprotected  ends. 
Connect field cables to the end with unprotected 
GREY terminal  blocks. Connect  cables  from 
the  equipment  to  be  protected  to  the  end 
with  ORANGE  terminal  blocks.  Connect 
the  ground  wires  to  the  GREEN  terminal 
blocks  on  their  respective  ends.  For 
AT78120 modules, use “1” for “LINE,” “2” 
for “NEUTRAL,” and “G” for “Ground” on 
both  incoming  and  outgoing  wires.  For 
AT87012  and  AT87024  modules,    use  “1” 
for  negative  (-),  “2”  for  positive  (+),  and 
“G”  for  “Ground”  on  both  incoming  and 
outgoing  wires. 

(see  figure  3  on  reverse 

side)

.

 

3.3 

COAX MODULE INSTALLATION 

Connect  the  incoming  line  to  the    port  marked 
“LINE” on the AT87 coax module. Run cable from 
the AT87 port marked “EQUIP” to the equipment 
meant to be protected. 

See Wiring Guide for more 

information.

 

3.4 

PTZ MODULE INSTALLATION 

Connect  the  incoming  line  to  the    side  marked 
“UNPROTECTED” on the AT87 PTZ module. Run 
cable  from  the  AT87  port  marked  “PROTECTED” 
to the equipment meant to be protected. 

For  wire 

insertion  instructions,  see  section  2.3  “AT87 

MODULES  WITH  CAGE  CLAMP  TERMINALS.” 

See Wiring Guide for more information. 

 3.5  CAUTION:  The  current-limiting  features  of 
CCTV  surge  protectors  could  be  rendered 
inoperable if improperly installed or not properly 
grounded 

2.3.1     Insert a small screwdriver into the upper 
hole  of the terminal block 

(see figure 2). 

2.3.2     Push screwdriver in and lever away from 
the  lower  hole  with  moderate  force.  This  will 
visibly open the cage clamp in the lower hole. 

2.3.3     Insert  wire  stripped  at  0.250”  into  the 
lower  hole.  Once  wire  is  positioned  correctly,  remove 
screwdriver from the upper hole. The wire is now 
secure. 

3. AT87 2-IN-1 AND 3-IN-1 INSTALLATION 

3.1 

Multiple  AT87  modules  can  be  combined 

onto  a  single  mounting  plate,  all  sharing  a 
common  source  of  ground  for  proper  surge 
protection.  Attach  a  minimum  #10  AWG  ground 
wire  with  the  supplied  nut,  washer,  and  ring 
terminal  to  the  ground  stud  on  the  underside  of 
the  mounting  plate 

(see  figure  1). 

The  metallic 

ground stud is the unit’s Earth connection. 

3.2 

POWER MODULE INSTALLATION 

Connect  the  incoming  line  to  the  AT87  module, 
using  either  the  grey/green  terminal  blocks 

(see 

section 2.3)

 or the 3.5mm socket (PS models only). 

Run  cable  from  the  AT87  module,  using  either 
orange/green terminal blocks or male 3.5mm plug 
to  the  equipment  meant  to  be  protected.  See 
Wiring Guide for more information.

 

Reviews: