Installation, Operation & Maintenance Guide

 

AtmosSmart 

12

1-888-MY-AIR11        CAG-06-21-003        AtmosAir.com

06 

 BMS  CONNECTIVITY

AtmosSmart is BMS compatible through BACnet IP. Ethernet connection is made from the AtmosSmart system to the BMS using 

RJ45/Cat5E cable. There are eight (8) BMS read points per AtmosSmart™ controller. (see list mentioned earlier) The AtmosSmart™ 

displays Real-Time IAQ Data to BMS. Optional AtmosAir also offer an optional outside air probe to read the incoming outside air. 
This can be connected to BMS using RJ45/ Cat5E cable (not supplied) AtmosAir also offers an optional BMS Remote On/Off Control 
of the AtmosAir BPI systems. 

07 

 ATMOSSMART/ATMOSCOMMS CONNECTIVITY & SEQUENCE

NOTE

: The two ends with receptacles of the AtmosSmart Sensor Probe are generally arranged as ‘network’ and ‘display’ on one 

end, and output to AtmosAir BPI Systems and Micro-USB on the other. If the AtmosAir BPI control cable is plugged into the wrong 
RJ-45 cable receptacle nothing will happen. Check for the correct RJ-45 receptacles.

Note/Warning

: All power must be off to both ends of the AtmosSmart System and AtmosAir BPI System. Once the two ends of the 

AtmosSmart/AtmosAir BPI system are installed/mounted, the installer should connect the following cables.

1. 

Main power Armorflex shrouded umbilical to 120 VAC to 250 VAC 50/60 Hz 15-amp dedicated service with known good ground 

via junction box. Umbilical is 10’ (3.05m) long. (Check to see main toggle switch is off).

2. 

Connect the supplied ethernet cable between the jack on the AtmosSmart unit to the AtmosComms2 controller.  

Note:

 This is the only jack on the AtmosComms2 system mounted under the ionizer that could receive this cable.

3. 

If you are connecting a second AtmosAir/AtmosComms2 to a single AtmosSmart, there is another RJ-45 Cat5e cable to connect. 

(See photos in AtmosSmart Capable Configuration Diagram).

4. 

Connect the Micro-USB ‘brick-type’ power supply to the same 15-amp dedicated as the AtmosAir system(s). This is to power the 
AtmosSmart module.

5. 

Connect HDMI cable to display (optional).

6. 

Connect RJ-45 port to network/BMS. Cable not supplied.

Power-Up and Commissioning

AtmosSmart derives its power from the main Armorflex umbilical. Assure there is power to the unit(s). 

Switch on main power toggle switch on AtmosAir 500 Series BPI system and the AtmosSmart IAQ probe. The AtmosSmart will 

automatically go into a 6-minute self-check and sensor warm up mode. The output display will indicate that it is self-checking and 

warming up the sensors. 

The display will start scrolling real time data after about 6 minutes. You may not see any indication of AtmosAir System operation 

immediately. 

Within 6 plus minutes the AtmosAir systems will start cycling and setting its parameters. 

You will know the AtmosAir system is responding to AtmosSmart commands by the red function light on the AtmosAir BPI unit 

which will periodically cycle on or off according to demand. 

When AtmosSmart is sensing and making air quality ‘decisions’ it is possible that the AtmosAir system’s red light may remain off 

for up to 30 seconds. The unit will self-start or re-start when the power is lost and regained.

Summary of Contents for AtmosSmart

Page 1: ...to its pure natural state where no pollution or contaminants exist while reducing energy use and emissions in the process AtmosAir com CAG 06 21 003 IMPORTANT Save this Document for Future Reference W...

Page 2: ...nd The electrical cable enclosed with your AtmosAir unit must be used as it has a special plug which provides a ground circuit for the equipment Always replace fuse with the same rating and type of fu...

Page 3: ...al Product Description 6 Mode of Operation 7 02 INSTALLATION 8 03 STEP BY STEP INSTALLATION INSTRUCTIONS 11 Installing AtmosAir 500 Series in a Duct 11 04 MONITORING DISPLAY INSTALLATION 12 05 ATMOSSM...

Page 4: ...Air Flow Sensor Differential Pressure Switch Optional Must be Ordered Control Capacity Up to 8 AtmosAir Ionization Systems Standard Unit 2 BPI Requires AtmosMultiplier 4 with Optional AtmosEXTender A...

Page 5: ...ing oxygen molecules are ionized which aid in cleaning indoor air General Product Description AtmosSmart is an integrated sensor array designed for installation in the RETURN duct of a typical HVAC ai...

Page 6: ...determining occupancy O3 Ozone HCHO Formaldehyde and PM Particulate Matter The IAQ readings can be output by attaching an HDMI capable display Display is accessible from a HDMI port located in the Se...

Page 7: ...lter if present or the AHU itself 02 INSTALLATION The Sensor Array is housed in a doubly insulated hi impact plastic enclosure which is placed in the duct work or AHU If placed in the duct a 3 8 8 cm...

Page 8: ...CH xxx BEND TWO PLACE DECIMAL xxx THREE PLACE DECIMAL APPLICATION USED ON NEXT ASSY PROPRIETARY AND CONFIDENTIAL THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF ATMOSAIR SOLUTIONS AN...

Page 9: ...above The sensor head reads multiple indoor air quality IAQ data sets in real time by sensing air properties in the Return Air system This configuration allows the sensor to adjust IAQ based on deman...

Page 10: ...tallation recommendations Each AtmosSmart enabled 500 series Matterhorn Series unit has an AtmosComms2 controller module integrally installed These controller modules communicate with the sensor array...

Page 11: ...om of the duct A mounting bracket is optional The display shows real time data and is read only It may be folded up out of the way A HDMI port is also provided in the Sensor Body A large remote monito...

Page 12: ...e supplied ethernet cable between the jack on the AtmosSmart unit to the AtmosComms2 controller Note This is the only jack on the AtmosComms2 system mounted under the ionizer that could receive this c...

Page 13: ...There are no user serviceable parts inside the sealed Sensor module Sensors will need to be replaced recalibrated generally after 2 calendar years Certified AtmosAir dealers will coordinate sensor mai...

Page 14: ...NS OF CLEAN AIR GROUP HERIN ARE EXPRESSLY GRANTED IN LIEU OF ALL WARRANTS WHETHER EXPRESS OR IMPLIED INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PUR...

Reviews: