Installation Requirement
7
PV-10PX / PV-10HPX
Concrete Specifi cations
Concrete specifi cations must be followed accordingly.
Failure to do so may result in lift and/or vehicle falling.
1. Concrete must have 4 inches minimum and must be totally cured before lift
installation.
2. Concrete must be in good condition and must have a test strength 3,000psi
minimum.
3. Floors must be level with no cracks or holes.
Fig. 4
Power Supply
220 volt single phase motor on a 30 amp breaker with minimum of 10 gauge
wire. Operating voltage range is 208v-230v.
4”