Biology (CFU/ml)
Type of cooling system
Standard
Energy recovery
Single pass
< 10
5
/
< 10
7
< 10
3
/
< 10
5
Recirculating (with tower)
< 10
5
/
< 10
7
not applicable
Closed loop
< 10
3
/
< 10
5
< 10
3
/
< 10
5
The table shows the recommended values. The values in
bold
are rejection limits.
If additives are used in the cooling water, take into account that the cooling capacity will
change.
Δm = ((C
pw
- C
pa
) * X) / (C
pw
*(1-X) + X*C
pa
) * 100 %
with
Δm: change of mass flow of the coolant
C
pw
: specific heat capacity of water
C
pa
: specific heat capacity of the additives
X: the percentage of additives
6.1.6
Energy recovery data
Reference conditions
See section
Reference conditions and limitations
Effective working pressure
See section
Compressor data
for the normal working pressure.
Maximum allowed pressure of the heat exchanger
Oil side
15 bar (217 psi)
Water side
10 bar (145 psi)
Reading settings
In addition to other data, the following temperatures can be read on the controller display:
For air-cooled units:
• The water inlet temperature of the energy recovery system
• The water outlet temperature of the energy recovery system
Modifying settings
If the programmed warning settings for the water temperatures are exceeded, a warning
indication is shown on the controller:
Instruction book
2920 7118 31
91
Summary of Contents for GA 11+
Page 1: ...INSTRUCTION BOOK OIL INJECTED ROTARY SCREW COMPRESSORS GA 11 GA 15 GA 18 GA 22 GA 26 GA 30 ...
Page 2: ......
Page 44: ... BOOT Software nr Instruction book 42 2920 7118 31 ...
Page 99: ...Prefilter components Reference Name 1 4 Prefilter Instruction book 2920 7118 31 97 ...
Page 151: ......