secondary of the transformer. The indicated fuse values are valid for the fuses to be installed by
the customer.
Setting motor overload relay (F21)
Overload relay and fuses
GA11+
GA15+
GA18+
GA22+
GA26+
GA30
Freq (Hz)
Voltage (V) (A)
(A)
(A)
(A)
(A)
(A)
IEC
50
230
27
38
45
51
70
69
50
400
16
22
26
30
41
40
60
230
27
42
46
50
60
69
60
380
16
21
26
30
37
42
60
460
13
18
21
25
30
35
UL/cUL
60
460
13
18
21
25
30
35
60
575
11
14
17
20
24
28
60
200
31
42
49
57
69
78
60
230
29
42
46
52
67
75
60
460
14
21
23
26
34
38
Setting fan motor overload protection (Q15/ F15)
Circuit breaker
GA11+
GA15+
GA18+
GA22+
GA26+
GA30
Freq (Hz)
Voltage (V) (A)
(A)
(A)
(A)
(A)
(A)
IEC
50
230
0.7
0.7
1.9
1.9
2.5
2.5
50
400
0.4
0.4
1.1
1.1
1.5
1.5
60
230
1
1
2.6
2.6
2.6
2.6
60
380
0.5
0.5
1.5
1.5
1.5
1.5
60
460
0.5
0.5
1.4
1.4
1.4
1.4
UL/cUL
60
460
0.5
0.5
1.4
1.4
1.4
1.4
60
575
0.7
0.7
1.2
1.2
1.2
1.2
60
200
1.1
1.1
3.3
3.3
3.3
3.3
60
230
1
1
2.8
2.8
2.8
2.8
60
460
0.5
0.5
1.4
1.4
1.4
1.4
Earthing
The earthing cable connected to the compressor (PE) should be minimum 10 mm
2
(according to
EN 60204-1 section 828).
Instruction book
2920 7118 31
131
Summary of Contents for GA 11+
Page 1: ...INSTRUCTION BOOK OIL INJECTED ROTARY SCREW COMPRESSORS GA 11 GA 15 GA 18 GA 22 GA 26 GA 30 ...
Page 2: ......
Page 44: ... BOOT Software nr Instruction book 42 2920 7118 31 ...
Page 99: ...Prefilter components Reference Name 1 4 Prefilter Instruction book 2920 7118 31 97 ...
Page 151: ......