Atlas Copco FD1200 Instruction Book Download Page 5

2920 1371 00

5

Instruction book

Oil-free Air Division

is warmed up by the incoming air to approx. 10°C (18°F)
below the incoming air temperature.  Reheating the dried air
reduces its relative humidity, so that condensation in the air
net cannot occur unless the air is cooled to below the pressure
dewpoint temperature indicated by gauge (1).

1.3 Refrigeration circuit (Fig. 2)

Compressor (M1) delivers hot, high-pressure refrigerant gas,
which flows, via the coil(s) of liquid separator(s) (7), through
condenser (9) where most of the refrigerant condenses.  On
air-cooled condensers, a fan control switch (S3) stops and starts
the fan motor (M2) at falling or rising condenser pressure.  On
water-cooled condensers, an automatic valve (3-Fig. 5a)
regulates the cooling water flow, thus controlling the
temperature, which is directly dependent on the pressure.  The
cooled refrigerant then collects in receiver (10).

The liquid leaves the receiver (10) via its syphon outlet and
flows through liquid refrigerant dryer (12), via refrigerant/
refrigerant heat exchanger (17) and sight-glass (8), to expansion
valve (13) where it expands to evaporating pressure.

In expansion valve (13) some of the expanding liquid refrigerant
evaporates, for which the required heat is withdrawn from the
refrigerant itself.

The refrigerant enters the heat exchanger/evaporator (15) where
it withdraws heat from the compressed air by further
evaporation.  Dependent on the compressed air load, all, or
almost all, refrigerant evaporates at constant pressure and
temperature.  The vapour refrigerant leaving evaporator (15)
flows into liquid separator(s) (7) via refrigerant/refrigerant heat
exchanger (17).  The liquid separator prevents any droplets
from entering compressor (M1) because warm refrigerant,
leaving the compressor, flows through the coil(s) of the liquid
separator(s) and evaporates the surrounding liquid.  From liquid
separator(s) (7) the refrigerant gas is sucked in by the
compressor.

The dryers are provided with a sight-glass (8).  The sight-glass
allows to check the refrigerant flow in the line.  During normal
operation, the liquid flow must be clear.  In general, vapour
bubbles indicate a shortage of refrigerant.  Note that fluctuations
in the load may cause bubbles to pass in the flow for a short
time.  The center of the glass is provided with a moisture
indicator which is green when the liquid refrigerant is free of
moisture.  It will turn into yellow when the refrigerant contains
moisture, indicating that the liquid dryer needs to be replaced.

1.4 Automatic regulation system

(Fig. 2)

Expansion valve (13) maintains the evaporating temperature
between 1 and -1°C (34 and 30°F); these are the approximate
limit temperatures at zero and maximum air load respectively.

At partial or no load, the excess cooling capacity is transferred
in liquid separator(s) (7).  The condenser pressure must be kept
as constant as possible to obtain stable operation of expansion
valve (13).  Therefore, on air-cooled dryers, fan control switch
(S3) stops and starts cooling fan (M2).  On water-cooled dryers,
the temperature is controlled by an automatic regulating valve
on the water circuit.  The switch or regulating valve ensures
proper operation at low air load and/or low ambient temperature.

1.5 Electrical system

These dryers are three-phase units.

The refrigerant compressors are equipped with a crankcase
heater.  When voltage is supplied, the heater is energized.  It
keeps the oil in the crankcase warm to prevent condensing of
refrigerant in the compressor housing, which could result in
serious damage of the compressor at restart (liquid knock).

F1.

Fuses, fan motor

F2/F3. Fuse, secondary side (24 V) of transformer
K1.

Motor contactor, refrigerant compressor

L1/3.

Terminal, mains

PE.

Earth terminal

T1.

Transformer

Fig. 3. Electric cubicle (typical example)

Summary of Contents for FD1200

Page 1: ...the requirements for instructions specified by the machinery directive 89 392 EEC and is valid for CE as well as non CE labelled machines Registration code Collection APC FD Tab 38 Sequence 987 No 292...

Page 2: ...ons must be performed by trained personnel from Atlas Copco who can also be contacted if any further information is desired In all correspondence always mention the dryer type and the complete serial...

Page 3: ...the water outlet of the condenser FD560 up to 950 are air cooled while FD560 W up to 1600 W are water cooled dryers The suffix W is not mentioned further in the book where the descriptions are valid...

Page 4: ...trap with automatic discharge 5 Automatic condensate drain hose 6 Manual condensate drain valve 7 Liquid separator 8 Sight glass with moisture indicator 9 Refrigerant condenser 10 Liquid refrigerant...

Page 5: ...of the liquid separator s and evaporates the surrounding liquid From liquid separator s 7 the refrigerant gas is sucked in by the compressor The dryers are provided with a sight glass 8 The sight glas...

Page 6: ...s tripped In such case the compressor will restart when the motor windings have cooled down which may take up to 2 hours An electronic thermostat with display and alarm functions is installed on the i...

Page 7: ...S3 Fan control switch 1 Condensate trap with automatic discharge 2 Refrigerant shut off valve 3 Condenser 4 Liquid refrigerant receiver 5 Fan 6 Sensor high pressure shut down switch 7 Refrigerant exp...

Page 8: ...e is reached Press key 5 or wait a few seconds to store the new value If the temperature increases above the preset value alarm indicator lamp H3 Fig 10 will light up An automatic interval drain 1 may...

Page 9: ...receiver 2 Condenser 3 Flow regulating valve 4 Refrigerant shut off valve 5 Electric cubicle Figs 5 Side views of water cooled FD units 6 Condensate trap with automatic discharge 7 Refrigerant shut o...

Page 10: ...2920 1371 00 10 Oil free Air Division Instruction book 2 INSTALLATION 2 1 Dimension drawings Figs 6 Fig 6a Dimension drawing of FD560...

Page 11: ...2920 1371 00 11 Instruction book Oil free Air Division Fig 6b Dimension drawing of FD560 W...

Page 12: ...2920 1371 00 12 Oil free Air Division Instruction book Fig 6c Dimension drawing of FD700...

Page 13: ...2920 1371 00 13 Instruction book Oil free Air Division Fig 6d Dimension drawing of FD700 W...

Page 14: ...2920 1371 00 14 Oil free Air Division Instruction book Fig 6e Dimension drawing of FD850 and FD950...

Page 15: ...2920 1371 00 15 Instruction book Oil free Air Division Fig 6f Dimension drawing of FD850 W FD950 W and FD1200 W...

Page 16: ...2920 1371 00 16 Oil free Air Division Instruction book Fig 6g Dimension drawing of FD1600 W...

Page 17: ...ve 2 Fig 8 onto the condensate drain pipe Lay out the condensate drain hose 3 Fig 8 via a funnel towards a drain collector to allow visual inspection The hose must pitch downwards away from the dryer...

Page 18: ...the dryer 7 Check that the primary side connection of the transformer T1 Fig 3 corresponds with the supply voltage 8 Check that the electrical installation corresponds to the local codes The dryer mus...

Page 19: ...he spindle fully out and refit the cap 3 On air cooled dryers press run stand by button S1 Check that the sense of rotation of the fan motor is correct Cooling air must be drawn in through the condens...

Page 20: ...ficient cooling water flow 2 Refrigeration system problems or maladjustment Maladjustment of the refrigerant expansion valve 7 Fig 4b and 9 Fig 5b Shortage of refrigerant in circuit through leakage Co...

Page 21: ...ntilated Local law may impose that work on the refrigerant circuit of the cooling dryer or on any equipment which influences its function should be executed by an authorized control body the installat...

Page 22: ...t temperature too high c See 1b d Condenser externally clogged d Clean the condenser e Insufficient cooling water flow e See 1c f Cooling water inlet temperature too high f See 1d 3 Compressor stops o...

Page 23: ...ooling water temperature C 45 45 7 2 Specific data Air dryer FD 560 W 560 HP W 700 W 850 W Location Indoors Indoors Indoors Indoors Medium to be dried Air Air Air Air Volume flow at dryer inlet at nom...

Page 24: ...50 Hz l s 0 8 1 2 1 6 60 Hz l s 1 2 1 6 Electric power input Air cooled 50 Hz l s 11 8 60 Hz l s Water cooled 50 Hz kW 10 7 12 3 18 6 60 Hz kW 14 8 22 3 Refrigerant Difluormonochlormethane CHF2Cl R40...

Reviews: