![background image](http://html1.mh-extra.com/html/atlantis/host-power-1101rc/host-power-1101rc_user-manual_3000592083.webp)
83
AVR
Vin(V)
AVR
Vout(V)
Note
Vin
≦
165V
N/A
Inv (220± 7%)
the UPS returns to AC
output mode when AC
input increase to 176V
166V
أ
Vin
أ
200V
Increase (15%)
206-250V
Vout(min)=206V
201V
أ
Vin
أ
239V
N/A
Vin
240V
أ
Vin
أ
274V
Decrease (15%)
204-233V
Vout(max)=233V
Vin
≧
275V
N/A
Inv (220± 7%)
The UPS returns to AC
output mode when AC
input drops to 264V