101
Technical Features
Model
A03-OP1001-RC A03-OP2001-RC A03-OP3001-RC
Release
Rel 19.0
Rel 19.0
Rel 19.0
Power Rating(VA)
1000
2000
3000
Power Rating(W)
900
1350
2700
IN
PUT
Low
Line
Transfer
160VAC(load <=80%), 140VAC(80%-70%), 120VAC(70%-
60%), 110VAC(load <60%) (±5%)
Low
Line
Comeback
170VAC, 150VAC, 130VAC, 120VAC (±5%)
High
Line
Transfer
300VAC (±5%)
High
Line
Comeback
290VAC (±5%)
Frequency Range
40Hz to 70Hz
Power Factor
>0,99 (Normal Voltage)
O
UT
PUT
Voltage:
200/208/220/230/240VAC
AC
Voltage
Regulation
±1%
Frequency
Range:
47-53Hz or 57-63Hz (Synchronized Range)
Frequency
Range:
50Hz (±0.1Hz) or 60Hz (±0.1Hz) (Bat. Mode)
Waveform
Pure SineWave
Crest Ratio
3:1 (Max)
Harmonic
Distortion
(THDU)
<2% THD (liner Load)
<4% THD (Non liner Load)
TR
A
N
SF
ER
AC->Battery
Zero
INV->ByPass
Less than 4ms (typical)
WaveForm
(Batt.
Mode)
Pure Sinewave
EFFICIENCY
AC Mode=90%
Battery=88%
ECO=97%
AC Mode=90%
Battery=89%
ECO=97%
AC Mode=91%
Battery=90%
ECO=97%
B
A
T
T
E
R
Y
Voltage
24VDC
36VDC
72VDC
Summary of Contents for A03-OP1001-RC
Page 1: ......
Page 5: ...5 A03 OPX001 RC_MX01 rel 19 0 2 2020...
Page 42: ...ITA 42 Sostituzione Batterie Battery Replacement Suono ogni 2 secondi...
Page 68: ...ENG 68 Step 3 Put the front panel back to the unit Rack Mount Installation Step 1 Step 2...
Page 69: ...ENG 69 Tower Installation Step 1 Step 2...
Page 76: ...ENG 76 EE EEprom error FA FAN BR Battery Replacement RAC Rack display TOE Tower display...
Page 98: ...ENG 98...
Page 100: ...ENG 100...
Page 107: ...Atlantis via C Chiesa 21 Pogliano Milanese MI 20010 Italy info atlantis land com...