17
EPIC 2D
Installation
M04 PUMP 1 / M05 PUMP 2
AUTOTUNING
AUTOSET: P1
XXXV XXA 09S
M04 PUMP 1
>AUTOTUNING
>EXIT
M04 PUMP 1
>AUTOTUNING
>AUTOTUNING
ON
AUTOTUNING
>ON
CHANGE NOMINAL CURRENT
NOM. CURRENT
>XXX.X
M04 PUMP 1
>NOM. CURRENT
>EXIT
M04 PUMP 1
>NOM. CURRENT
>NOM. CURRENT
000.1
NOM. CURRENT
>000.0
ACCESS TO FUNCTION
MODIFIED PARAMETERS
>M04 PUMP 1
M05 PUMP 2
The amperage value shown on the display may differ
± 5% from the nominal value of the pump (nameplate
data) since the control panel is not a measuring
instrument. The same value may differ depending on
the operating conditions of the installation.
AUTOTUNING
It allows the self-learning of the data to be carried out again
NOMINAL CURRENT
Set nominal/operating current of the pump
MINIMUM AMPERAGE
Current setting min. for dry running protection
MAXIMUM AMPERAGE
Max current setting for overcurrent protection
START PER HOUR
Set max number of pump starts per hour