4.1 Configuration 1, 2, 3 or 4:
heat pumps with electric back-ups
"
Parameter 5700.
Configuration 1
: 1 heating circuit (see figure
page 45
).
Configuration 2
: 1 heating circuit and DHW tank. (see figure
page 46
).
Configuration 3
: 2 heating circuits (see figure
page 47
).
Configuration 4
: 2 heating circuits and DHW tank. (see figure
page 48
).
DHW tank control (with electrical back-up) requires the
use of the DHW kit.
The control of 2 heating circuits requires the installation
of the 2
nd
circuit.
4.1.1 Hydraulic connections
"
In the case of a mixed DHW tank.
Install the directional valve on the heating circuit
(on circuit 2 if it exists).
"
In the case of 2 heating circuits.
With the 2
nd
circuit kit, the hydraulic unit's circulation
pump (CC1) must be moved and installed in a box of
the 2
nd
circuit kit (CC1).
4.1.2 Electrical connections
• 1
- Power supply to the outdoor unit.
Please refer to section (Electrical connections on the
outdoor unit side
page 24
).
• 2
- Interconnection between the outdoor unit and the
hydraulic unit (see
figure 37 , page 26
).
• 3
- Power supply to the electrical back-ups :
-Connect the electrical supply for the back-ups
(terminals 20, 21, 22 and 23) to the electrical panel.
(see
figure 37, page 26
).
• 4
- Outdoor sensor (see
figure 38, page 27
).
• 5
- Room thermostat and/or room control unit (Option,
see
figure 38, page 27
).
• 6
- Contract with the power provider :
-Connect the "Power Provider" contact to input EX5 or
EX4. (see
figure 38, page 27
)
"
In the case of a mixed DHW tank.
Please refer to the instructions supplied with the DHW
kit.
• 7
- Connect the directional valve to connector QX4,
(see
figure 38, page 27
).
• 8
- Connect the domestic water sensor to terminal
BX1 on the heat pump’s control panel (see
figure 38,
page 27
).
• 9
- Connect the back-up resistance to terminal 19
(Earth) and relay RP EPS to terminals 2 (L) and 4 (N)
(see
figure 37, page 26
).
• 10
- Connect the electrical power supply for the
domestic water back-up (terminals 17, 18 and 19) to
the electric panel (see
figure 37, page 26
).
"
In the case of 2 heating circuits.
Please refer to the instructions supplied with the second
circuit kit.
• 11
- Circulation pump CC2.
• 12
- Circulation pump CC1.
• 13
- Mixer valve.
• 14
- Initial sensor.
• ()
- Interconnection between RVS / AVS.
"
In the case of a heated floor.
Heated floor thermal safety fuse.
• 20
- The installer is responsible for connecting the
heated floor’s safety system. Thermal safety will stop
the heat pump if the temperature in the floor is too high.
4.1.3 Parametering the setting
• Adjust the configuration:
1
,
2
,
3
or
4
, Line
5700
.
• Adjust the DHW programme (Line
1610
to
1661
).
• 1 heating circuit.
Adjust the heating curve slope.
Line
720.
• 2 heating circuits.
Adjust the heating curve slope.
Line
720
(Circuit 1).
Line
1020
(Circuit 2).
4.1.4 Higher temperature radiators
• Possibility to adjust the temperature setpoint of the
radiator circuits.
Line
741
(Circuit 1).
Line
1041
(Circuit 2).
• First, adjust the value of the Switch-off temperature
max line
2844
.
4.1.5 Special cases
Please consult us regarding any other installation
configuration.
Installation and operating manual "1363 - EN"
- 45 -
Heat pump alféa S excellia 3-phase