Hot Water (HW)
"
Comfort T° charge
":
DHW p off-peak hours / Off-peak hours / Permanent.
Electrical back-up power:
0 to 20 KW.
Configuration
Comfort T° charge
Electrical back-up power
1KW
DHW Circuit
DHW p off-peak hours
Use the same procedure as the time program of heating periods. Resume from the step
2
(See
"Time programming",
page 56)
.
DHW period factory setting: 00:00 - 05:00, 14:30 - 17:00.
"
Comfort T°
":
ECO Temp Setpoint … 65°C.
"
ECO T°
":
8°C... Comfort Temp setpoint.
DHW temperature factory settings: Comfort 55°C, ECO 40°C.
Setpoint settings
Comfort T°
55°C
ECO T°
40°C
DHW Circuit
"
Anti-legionella
":
Stop, ON.
"
Day of treatment
":
Monday / Tuesday / Wednesday / Thursday / Friday / Saturday /
Sunday.
"
Hour of treatment
":
00:00.
"
Setpoint T°
":
55°C... 95°C.
Anti-legionella management
Day of treatment
Sunday
Anti-legionella
Stop
Hour of treatment
---
Setpoint T°
60°C
DHW Circuit
Some settings (or menus) might not be displayed. They are dependent on the installation's configuration (and installed options).
Hydraulic configuration
Hot water
General Configuration
Time programming
Setting setpoint T°
Anti-legionella management