Line
Function
Setting range
or display
Setting
increment
Basic
setting
Inputs / outputs test
7700
I
Relay test
0
This consists of instructing the regulator's relays one by one and checking their outputs. This enables you to check that
the relays are working and that the cabling is correct. Check that each appliance in the installation is operating correctly.
(0) No test, (1) Everything is on STOP, (2) Relay output QX1 : heat pump CC1 (Main regulation board), (3) Relay output QX2 :
Electrical back-up (1st stage) or Boiler connection distribution valve, (4) Relay output QX3 : Electrical back-up (2nd stage) or
Boiler connection contact, (5) Relay output QX4 : DHW distribution valve, (6) Relay output QX5 : DHW Electrical back-up,
(7) Relay output QX6 , (8) Relay output QX31 : Heat circ mix valve open Y1 (or control pilot-wire) , (9) Relay output QX32 : Heat
circ mix valve close Y2, (10) Relay output QX33 : heat pump CC2, (11) Relay output QX34, (12) Relay output QX35 : Swimming
pool distribution valve, (13) Relay output QX21 module 1, (14) Relay output QX22 module 1, (15) Relay output QX23 module
1, (16) Relay output QX21 module 2, (17) Relay output QX22 module 2, (18) Relay output QX23 module 2, (19) Not used, (20)
Not used, (21) Not used.
The display shows the “Key” symbol. Pressing the Info button displays "Error 368".
Warning: The component being tested is receiving electrical power throughout the test.
7710
I
Output UX1 test (3-phase electrical back-up command) 0... 100%
1
--
7712
I
PWM signal UX1
0... 100%
1
0
7716
I
Output UX2 test
0... 100%
1
--
7719
I
PWM signal UX2
0... 100%
1
0
7722
I
Digital output DO2
Off, On
Off
7723
I
Heat pump D3
Off, On
Off
7724
I
Outputs test UX3 ("Inverter" command)
0... 100 %
--
7725
I
Voltage value (Ux3)
0... 10 v
--
7804
I
Sensor temperature BX1 (HP flow temperature)
-28... 350 °C
--
7805
I
Sensor temperature BX2 (HP return temperature)
-28... 350 °C
--
7806
I
Sensor temperature BX3 (DHW temperature)
-28... 350 °C
--
7807
I
Sensor temperature BX4 (Outside temperature)
-28... 350 °C
--
7808
I
Sensor temperature BX5
-28... 350 °C
--
7809
I
Sensor temperature BX6
-28... 350 °C
--
7830
I
Sensor temperature BX21 module 1
-28... 350 °C
--
7832
I
Sensor temperature BX21 module 2
-28... 350 °C
--
7847
I
Contact status H2, module 2
Open, Closed
Open
7911
I
Input EX1 (Power shedding, EJP)
0, 230 V
--
7912
I
Input EX2 (Tariffs day/night)
0, 230 V
--
7913
I
Input EX3 (External fault)
0, 230 V
--
7973
I
Sensor temperature BX31 (Mixed circuit temp.)
-28... 350 °C
--
7974
I
Sensor temperature BX32
-28... 350 °C
--
7975
I
Sensor temperature BX33
-28... 350 °C
--
7976
I
Sensor temperature BX34
(Swimming pool exchanger temperature)
-28... 350 °C
--
7977
I
Sensor temperature BX35
-28... 350 °C
--
7978
I
Sensor temperature BX36
-28... 350 °C
--
7996
I
Contact status H33
Open, Closed
Open
Installation and operating manual "1572 - EN"
Heat pump air/water split 2 services alféa excellia duo
- 52 -