No.2 fire alarm control panel to the No.20 fire alarm control panel) will execute the

 

corresponding operation; and if the said key on an zone fire alarm control panel is

 

pressed, only the state of the zone fire alarm control panel will be changed. If the

 

RESET key on the concentrator is pressed by an operator when an zone fire alarm

 

control panel in the networked system is in the set state, the zone fire alarm control

 

panel will immediately respond to the restoration command and the file is set by it at

 

that time will lose the content updated this time, namely the data newly set after the

 

last time saving will not be saved automatically. Therefore, when the networked

 

system is debugged by several debugging personnel at the same time, it is

 

necessary to disconnect the networking cables of the set fire alarm control panel

 

temporarily before inputting mass data.

 

10) Selection and query of the content on the LCD

 

In this part, there are four keys, including 

▲, 

SELECT, 

CONFIRM 

and 

▼ 

. The specific

 

meanings of the four keys depend on the content currently displayed on the screen. The four keys

 

mainly have two applications:

 



Query alarms:

 

▲ 

: Upward rolling

 

SELECT: Select the activity area (fire alarm

 

request/feedback area, fault area).

 

CONFIRM: 

Confirm the activity area (fire alarm

 

request/feedback area, fault area).

 

▼ 

: Downward rolling

 



Input the

 

area,

 

area,

 

                password:

 

▲ 

: Move the cursor

 

upward.

 

SELECT: Select a figure.

 

CONFIRM:

Confirmthe

 

completion of password

 

inputting.

 

▼ 

: Move the cursor

 

downward.

 

11) Reserved keys for reserved functions

 

      Keys like F1, F2, F3, F4, 

◄ 

and 

► have no practical meanings at present and are

 

reserved for future system expansion.

 

12) Functional key lock

 

                                             

△ 

Caution: The key lock functions are designed for multi-line

 

                                      linkage control units only.

 

!

 

PERMIT

 

  PRHB.

 

AUTO

 

MANUAL

 

       

“PERMIT/PRHB.” key lock function: When the “PERMIT/PRHB.” key

 

lock is put on the PERMIT position, the system’s multi-line linkage function

 

will be enabled; and when it is put on the PRHB. position, the system’s

 

multi-line linkage function will be disabled.

 

       

“AUTO/MANUAL” key lock function: When the “AUTO/MANUAL” key

 

lock is put on the AUTO position, the multi-line linkage control units will run

 

automatically and priority will be given to the manual mode. In case a

 

piece of fire alarm information discovered in the system, the

 

corresponding multi-line linkage control unit will run automatically. When it

 

is put on the MANUAL position, the multi-line linkage control units can only

 

be started manually. At this time, the system can give alarms only and the

 

multi-line linkage control units will fail to run automatically.

 

- 15 -

 

Summary of Contents for ATL-9000 Series

Page 1: ...m Control Panel Linkage Type ATL 9000 SERIES ATL 9000 2 ATL 9000 4 ATL 9000 6 Angel Technologies Hongkong Ltd Add 3 F South Gate Chuangsheng Building XiIi Twon Yangguang Industrial Zone Nanshan Distri...

Page 2: ...rations of the system into Chinese The system can realize comprehensive on site programming and solve complicated linkage relation settings The system simulates the operating interfaces of Windows and...

Page 3: ...arm linkage mode and has a total of 324 intelligent detectors or modules for a single circuit The addresses of the intelligent detectors or modules may be hashed with No 1 to No 324 It is equipped wit...

Page 4: ...rities making system administration convenient It can realize local or remote software upgrades thus enabling it to operate stably and reliably Executive standards Fire Alarm Control Units GB4717 2005...

Page 5: ...panel Fire display panel 1 L 1 L PH O NE A LA R M Powersupply PRE SS HER E 1 3 System schematic diagram CFT QGL 9000 CFT QGL 9000 Intelligent 80 L smoke detector 80 L Intelligent heat detector Intell...

Page 6: ...terface board has two circuits Each of the two circuits can drive 324 intelligent detectors or modules Fire detector The system can be accessed to multiple intelligent smoke heat or composite detector...

Page 7: ...chnical parameters of the products of the system 1 5 1 Power supplies Main power supply AC 220V 20 50Hz or DC24V Emergency power supply Maintenance free DC24V battery its capacity depends on the syste...

Page 8: ...mensions of system engineering 2 1 Outline drawing and dimensional drawing of the product Appearance and dimensions of CFT QTL 9000 Main control unit Manual control unit Linkage unit Blank cover Print...

Page 9: ...Appearance and dimensions of CFT QGL 9000 Host cover Manual control unit Linkage unit Keyboard mouse Printer Blank cover Fig 2 2 Cabinet Dimensions 7...

Page 10: ...Lashing eye Scale3 1 Lashing eye Scale3 1 Inlet wire Fig 2 3 CFT QBL 9000 diagrammatic sketch 8...

Page 11: ...key and so on After checking the above do necessary inspections for the appearance of the fire alarm control panel If any non conformities are discovered in the check or inspections call our salesper...

Page 12: ...he insulation resistances between the buses of different circuits and that between the buses and ground as well as the loads of the circuits The insulation resistances should be larger than 20M and th...

Page 13: ...ANCEALARM OPERATIONDELAY POWER FAULT HO RN STROBEFAULT C MN AOM U IC TION SURVEILLANCEFAULT SYST TESTEM AUTO MANUAL K OREYB A D ISO TIOLA N GN AE ER LL KGIN A E R ETES SO N ERUDLIN A EKG SELE TC SSE T...

Page 14: ...en a fire alarm triggers a linkage and it will go out when all the linkage delays have ended and all the linkages have been established It will be lit when a power supply alarm of the fire alarm contr...

Page 15: ...power failure and is then powered on again the integration control state before the power failure will be restored User s Tip Integration refers to the integration control except for the sounder Sound...

Page 16: ...larms for the alarm information of the bus equipment The fault information of the interface boards the power supplies the printer the display panels and the communication of the fire alarm control pan...

Page 17: ...re alarm request feedback area fault area CONFIRM Confirm the activity area fire alarm request feedback area fault area Downward rolling Input the area area password Move the cursor upward SELECT Sele...

Page 18: ...upy 30 continuous bus module addresses The quantity of the manual control panels that may be accessed to a fire alarm control panel depends on the quantity of the interface boards There are 11 initial...

Page 19: ...US TNE TR B U STNE TRB U SENT TRB US TNE TR B U STNE TRB U STNE Fig 7 1 Multi line Linkage Control Unit The quantity of the multi line control points that may be accessed depends on the quantity of th...

Page 20: ...nd d Check whether there are linkage setting data in the linkage setup or not or whether the Register option in the linkage data is selected or not After the system reports a fire alarm linkage may be...

Page 21: ...rol panel nor slave fire alarm control panel s in the networked system Only after another fire alarm control panel has its number registered can the alarm information of the current fire alarm control...

Page 22: ...ely The other two yellow lights are respectively the short or open circuit lights for the No 1 circuit and the No 2 circuit There are two circumstances of open circuit Complete open circuit or partial...

Page 23: ...0 Positive pressure fan 11 Blow valve 12 Air blower 13 Fire damper 14 Fire door 15 Deluge valve 17 Spray pump 18 Stabilizing pump 19 Fire pump 20 Foam pump 21 Water curtain pump 22 Municipal electrici...

Page 24: ...1 L2 J k1 J k 2 S p 1 S p 2 J k1 J k 2 S p 1 S p 2 J k1 J k 2 S p 1 S p 2 9000 series host Bro a d ca stin g m o d u le Bro a d ca stin g m o d u le Bro a d ca stin g m o d u le 485 Bus Louds peak er...

Page 25: ...y 485 Bus Fault input 485 bus hub 1 2 3 4 5 6 Remot e B ackup Self control power inspection Publicf ailure Circ uit 1 Circ uit 2 DC2 4 Output Input Output 1 2 3 4 5 6 Broadc as ting c ontroller Broadc...

Page 26: ...A N interface Constant vol tage i nput 1 Constant vol tage output 1 Constant vol tage i nput 2 Constant voltage output 2 Amplifier failure input 1 2 RS485 A B Line C output GND 24 E CAN CAN HL C asca...

Reviews: