GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire) 

GSCM-MINI-D

ATKINSON ELECTRONICS, INC.

REV 07/08

Web Site: www.atkinsonelectronics.com

Distributed by:

OPTION #1  MOMENTARY START CONTACT  -  TYPICAL GENERATOR W/ STARTER CONTROL BOX

The GSCM-mini-D option #1 provides the same momentary glow plug operation for those 3 wire diesel applications where the key switch
or off button is pressed for 10 seconds energizing the glow plugs, then the start button is pressed starting the generator. The GSCM-
mini-D energizes K2 for 10 seconds to heat the glow plugs, then energizes K1 relay, providing a signal to the start/crank input and
removes it  when the generator has reached 45Hz, or half speed.   The K2  relay also provides a momentary “stop” signal until the
generator AC Hz has dropped to zero.  For operational sequence details see Page 4, Section - 1

  

OPTION #2  MAINTAINED START CONTACT TYPICAL GENERATOR W/ STARTER CONTROL BOX

The K1 relay provides a continuous run signal for generators

A double pole “kill switch” wired and installed by the user, stops

requiring a “maintained” start signal.  The K2  relay provides a

the generator instantly in emergency situations such as a fuel

momentary “stop” signal until the generator AC Hz has

spill.  One switch pole (N.C.) kills power to the GSCM-mini-D

dropped to zero.  For GSCM-mini-D operational sequence

opening all relays.  The other switch pole (N.O.) shorts out the

details see Page 4, Section - 2

magneto for an instant stop.

    

OPTION #3  IGNITION KEY SWITCH TYPE START CONTACT TYPICAL GENERATOR W/ STARTER CONTROL

The K1 relay is used to switch the starter input that is looking

A single pole “kill switch” wired and installed by the user, stops

for a momentary signal and opens it  when the AC line output

the generator instantly in emergency situations such as a fuel

has reached 45Hz. The K2  relay provides a continuous run

spill.  One switch pole (N.C.) kills power to the GSCM-mini-D

signal for generators requiring a “maintained”  ignition signal.

opening all relays shutting down the ignition switch type

When the GSCM-mini-D no longer receives a run command,

generators. 

K2 relay opens telling the generator to shutdown.  For GSCM-
mini-D operational sequence details see Page 5, Section - 3

Summary of Contents for GSCM-MINI-D

Page 1: ...Section 1 for operation description Maintained Start Contact Option 2 terminal 6 is grounded The GSCM mini D changes to a maintained start operation for generators that use a maintained closed contac...

Page 2: ...RATOR START CONTROL MODULE MINI 2 Wire to 3 Wire GSCM MINI D ATKINSON ELECTRONICS INC REV 07 08 Web Site www atkinsonelectronics com Distributed by GSCM mini D WIRING DIAGRAM AND CONTROLLER CONFIGURAT...

Page 3: ...wired and installed by the user stops requiring a maintained start signal The K2 relay provides a the generator instantly in emergency situations such as a fuel momentary stop signal until the genera...

Page 4: ...fuel problem etc the start sequence will revert to the Ready mode after a 60 second delay During this delay the start LED will blink rapidly The GSCM mini D will then try to start the generator again...

Page 5: ...remains closed until either the generator starts or the maximum cranking time period 20 seconds is reached 2 If the generator fails to start after the 20 seconds cranking period K1 relay opens for a...

Page 6: ...RTING FOR BATTERY CHARGING SECTION 6 The GSCM mini D can monitor either the generator battery voltage or a battery bank voltage and Automatically start stop the generator based on battery voltage This...

Page 7: ...elay after start signal removed before generator started 2 Generator Hz fast blink over speed condition Shutdown slow blink under speed condition double blink Maximum Crank attempts reached Failed to...

Page 8: ...long with the remote fault 12vdc light Turning off the power to the GSCM mini resets the fault condition and it is ready to receive another start command APPLICATION 3 GenMate PC BOARD REPLACEMENT The...

Page 9: ...ch appear within two 2 years from the date of shipment by Atkinson Electronics Inc or its authorized distributors to the original Customer Atkinson Electronics Inc will repair or replace at our option...

Reviews: