GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire) 

GSCM-MINI-D

ATKINSON ELECTRONICS, INC.

REV 07/08

Web Site: www.atkinsonelectronics.com

Distributed by:

FEATURES & APPLICATIONS

  

v

v

Inexpensive 2 wire to 3 wire start controller for
electric start 3 wire DIESEL & Gas  generators.

v

v

Optimized for use with Outback Invertors.

v

v

Supports three types of 3 wire generator control 
(momentary, maintained, ignition).

v

v

Fixed Crank time, Over and Under Hz shutdown,
and optional battery charging thresholds.

v

v

Maximum Auto-start Run Time Limit (6 hours)

v

v

Remote Run and Fault indication included. 

v

v

Totally sealed for harsh environment operation

  

DESCRIPTION 

  

The GSCM-mini-D is a micro-processor based generator
start-stop module, designed to auto start-stop high speed gas
and diesel generators needing a 3 wire connection from a 2
wire 12 volt manual start command.   It automatically
disconnects  the starter when a minimum generator AC Hz.
output  is measured, it can monitor  the generator’s output,
shutting  it down if either an over or under Hz condition is
detected.  LEDs are flashed to indicate the cause of the
shutdown.  Manually resetting the GSCM-mini-d (by removing
the power), removes the lockout and allows the generator to
restart if called to do so.  The GSCM-mini-D is powered by
12VDC from the generator battery, and can monitor the battery
voltage and start the generator to charge it’s own battery. All
Thresholds are fixed. The GSCM-mini-D is a limited function
controller, part of the GSCM family. If adjustability is required
use the GSCM full function Generator Start Control Module.

  

THREE MODES OF RELAY OPERATION

  

The GSCM-mini-D’s two relay contacts can be configured for
three types of three wire start/stop hook-up configurations;
momentary,  maintained and Ignition for Honda

s

, Onan

s

,

Yamaha

s

,  and other brands of generators.  This is

accomplished with an optional jumper on terminal 6.

  

Momentary Start Contact Option #1,

 terminal 6, has No

Connection. The GSCM-mini-D defaults to a momentary crank

battery systems. If adjustability is required then use the GSCM

operation for those generators that use two momentary push
button switches to start and stop the generator.  K2 energizes
for 10 seconds for diesel glow plug operation then, K1 cranks
the Starter. On shutdown, K2 momentarily grounds the
magneto.  See Section 1 for  operation description.

  

Maintained Start Contact Option #2,

 terminal 6, is

grounded. The GSCM-mini-D changes to a maintained start
operation for generators that use a maintained closed contact
to start (K1).  The generator is stopped by opening K1 and
closing K2 contact, momentarily grounding the magneto. See
Section 2 for operation description.

  

Ignition Key Switch Start Contact Option #3,

 terminal 6, is

connected to B+ (12VDC).  The GSCM-mini-D simulates an
automobile   ignition switch, K2 closes, maintains a closed
ignition contact for the generator to run and K1 closes
momentarily to crank the starter motor.  and de-energizes
when the start signal is removed. The K1 relay operates in a
momentary crank configuration. See section 3 for operation
description.

LED INDICATION DESCRIPTION 

  

The GSCM-mini-D has six indication LEDs. The 

Start LED,

blinks every 5 seconds to indicate ready for a start signal, blinks
every  2.5 sec. to indicate running in Auto Start mode, ‘On’
continuously indicates running in Manual Start mode. 
The 

Generator Hz LED,

 blinks to indicate over/under Hz Fault

and Start Failure do to Maximum crank attempted. A slow blink
indicates an under Hz condition, a fast blink indicates an over Hz
condition.  ‘On’ continuously indicates AC present in a non run
condition. A double blink indicates a start failure condition. The

Run LED

, ‘On’ continuously indicates a valid Run signal from the

generator.  The 

Fault LED

,‘On’ indicates a Fault condition has

occurred and GSCM is in lockout and must be reset.  The 

K1

and K2 LEDs

 indicate the relay status.

  

OPERATIONAL THRESHOLDS

  

The GSCM-mini-D has fixed operational thresholds. Those are:
Crank delay, Maximum Crank time, Crank Hz. Disconnect,
Under Speed Shutdown, Over Speed Shutdown, Max auto start
run time, and auto detects the Battery voltage to determine the
auto start and auto stop threshold values for 12V, 24V, and 48V

full function control module.

   

Crank delay:

 5 seconds

Maximum Crank:

20 seconds

Crank Disconnect:

45Hz

Under Speed Shutdown:

55Hz

Over Speed Shutdown:

65Hz

Max Auto Start Run time:

6Hours

Auto Start/Stop
Thresholds:

  Start

Stop

12V system

11.5V

13.8V

Standard

24V system

23.0V

27.6V

Call for option

48V system

46.0V

55.2V

Call for option

  

Relay Configuration:

Open input = Momentary Crank

(TERMINAL 6)

Grounded input = Maintained Crank
B+ (12VDC) input = Ignition & Crank

  

Fault Detection:

Start Failure, (3 attempts) 
Over Hz condition (10 seconds)
Under Hz condition (10 seconds)
Max Run time Auto restart within 30m
Generator stops due to its own fault condition

Summary of Contents for GSCM-MINI-D

Page 1: ...Section 1 for operation description Maintained Start Contact Option 2 terminal 6 is grounded The GSCM mini D changes to a maintained start operation for generators that use a maintained closed contac...

Page 2: ...RATOR START CONTROL MODULE MINI 2 Wire to 3 Wire GSCM MINI D ATKINSON ELECTRONICS INC REV 07 08 Web Site www atkinsonelectronics com Distributed by GSCM mini D WIRING DIAGRAM AND CONTROLLER CONFIGURAT...

Page 3: ...wired and installed by the user stops requiring a maintained start signal The K2 relay provides a the generator instantly in emergency situations such as a fuel momentary stop signal until the genera...

Page 4: ...fuel problem etc the start sequence will revert to the Ready mode after a 60 second delay During this delay the start LED will blink rapidly The GSCM mini D will then try to start the generator again...

Page 5: ...remains closed until either the generator starts or the maximum cranking time period 20 seconds is reached 2 If the generator fails to start after the 20 seconds cranking period K1 relay opens for a...

Page 6: ...RTING FOR BATTERY CHARGING SECTION 6 The GSCM mini D can monitor either the generator battery voltage or a battery bank voltage and Automatically start stop the generator based on battery voltage This...

Page 7: ...elay after start signal removed before generator started 2 Generator Hz fast blink over speed condition Shutdown slow blink under speed condition double blink Maximum Crank attempts reached Failed to...

Page 8: ...long with the remote fault 12vdc light Turning off the power to the GSCM mini resets the fault condition and it is ready to receive another start command APPLICATION 3 GenMate PC BOARD REPLACEMENT The...