GSCM Initialization and Adjustment 

 

1.

 

Powering up the GSCM with a jumper placed on reset terminals 7 and 8 will cause it to enter the adjustment mode. When 
the crank delay LED is lit the GSCM will accept timing modifications to any of the factory settings. See diagram in GSCM 
ADJUSTMENT CHART, which describes each adjustment LED and the setting that it refers to
. Connect your digital volt 
meter between the test point and ground (terminal 15) to read the settings. 

2.

 

In the adjustment mode, the GSCM first lights the crank delay LED and outputs the current setting value to the test point 
where it can be read with the digital volt meter. 

3.

 

Pressing the advanced up or down buttons allows the user to scroll through the ten settings, reading the value with the 
meter. 

4.

 

To change a stored setting, scroll to the desired setting indicated by the LED. Press the change/ store button once. The 
LED will then begin to blink indicating the unit is ready to accept a new value. The test point voltage now can be changed 
by pressing either the up button to increase the value or the down button to decrease the value. See chart in GSCM 
ADJUSTMENT CHART

5.

 

To store the new value, press the change/ store button once again, and the new value is then stored to the memory. If 
you do not want to modify the value, but have pressed the change/ store button by accident, pressing the change/ store 
button will restore the displayed value and take you out of change mode. 

6.

 

To disable the 5 minute start delay timer used in battery charging applications, jumper between terminals 15 and 16 
(override 12 hour shutdown) while adjusting the cut-in voltage set point.  Remove jumper after the new cut-in adjustment 
has been stored See AUTOMATIC STARTING FOR BATTERY CHARGING section: 1-3

7.

 

To disable the 10 minute stop delay timer, jumper between terminals 15 and 16 while adjusting the cut-out voltage set 
point. Remove jumper after the new cut-out adjustment has been stored. See AUTOMATIC STARTING FOR BATTERY 
CHARGING section: 1-3.
 

8.

 

To disable the over/ under Hz fault shutdown, advance to the low Hz position, press the change/ store button, (led blinks) 
and set the test point voltage to 0VDC, store setting, advance to high Hz position and set to zero volts, both must be set. 

9.

 

To re-enable the 5 and 10 minute time delays, the GSCM must enter adjustment mode as in paragraph 1 of this section 
and then the cut-in and cut-out adjustment re-entered and stored without the jumper between terminals 15 and 16. 
Restoring the GSCM factory default values as described in GSCM Reset Conditions: 6 will restore the time delays. 

10.

 

Switched signal using the battery voltage sensing input such as application 5 and application 6 requires that the cut-in and 
cut-out adjustments to be set to +5V @ test point while in setup mode. 

11.

 

After scrolling through all the settings to verify that any changes made have been stored, removing the reset jumper on 
reset terminals 7 and 8 will cause the GSCM to enter the ready mode and the start LED blinks once each 5 seconds to 
indicate that the GSCM is ready to receive a manual or auto start signal. See GSCM STARTING SEQUENCE section

12.

 

During the ready mode, applying a reset of 30 seconds by shorting the reset terminals will start the 30 day exercise period 
if it has been selected by adjusting the exercise time above a zero volt signal. Short term GSCM module power 
interruptions will not change this 30 day exercise cycle start time. 

13.

 

The three push buttons are ignored except in the adjustment mode described above. 

GSCM Reset Conditions 

 

1.

 

Shorting the reset terminals momentarily when the GSCM is starting, but not yet running, causes the generator start 
sequence to terminate and a 60 second delay period (with the start LED blinking rapidly) it must pass before the 
generator can start again. 

2.

 

Shorting the reset terminals during this delay period terminates the period and puts the GSCM into ready mode waiting 
for a new start command signal. 

3.

 

Shorting the reset terminals momentarily while the generator is running terminates the run command and the GSCM 
causes the generator to go through a normal shutdown sequence. 

4.

 

Shorting the reset terminals momentarily while the generator is locked out in a fault condition terminates the shutdown 
and enters a 60 second delay period (with the start LED blinking rapidly) before the generator can start again. 

5.

 

Resetting the GSCM for 30 seconds while in the ready mode is required to start the 30 day exercise period after which the 
30 day LED blinks if it has been selected by adjusting the exercise time above a zero volt signal. 

Summary of Contents for A0217

Page 1: ...Generator Start Control Module Part GSCM Rev C Code Version 5 13 ATKINSON ELECTRONICS INC 14 West Vine Street Murray Utah 84107 ...

Page 2: ... not already running before trying to start a second or third time Features Applications Automatic starting load transfer and shutdown for gas and diesel generators Off grid generators Automatic adjustable voltage set points for generator battery charging applications 0 60VDC Works with 12 24 or 48V battery systems Provides fault shutdown for low oil pressure high temperature and under speed or ov...

Page 3: ...e is set at 0 de activated The GSCM provides a 30 day exercise function which can be synchronized with a photo voltaic input to only start each 30 day period at the beginning of the solar charge day A user supplied DC relay can be energized during the 30 day generator exercise to override a battery charger and allow the battery bank to equalize by charging the batteries above the normal charger cu...

Page 4: ...www atkinsonelectronics com Circuit Board Division 800 261 3602 4 Revised 09 18 GSCM Wiring Diagram ...

Page 5: ...e maximum crank lockout condition This lockout condition remains until the GSCM is reset by momentarily shorting the reset terminals 7 and 8 together after which the start LED blinks for 60 seconds and then enters ready mode Powering down the GSCM for 5 seconds and powering it back up will also clear the maximum crank lockout condition with the GSCM returning to ready mode 6 When the generator sta...

Page 6: ...ins 7 and 8 momentarily The open collector transistor terminal 18 will energize a user supplied DC relay not exceeding 180 milliamp coil current whenever a fault shutdown occurs and will de energize the relay when the fault is reset The shutdown conditions are as follows 1 Failure to start with 4 cranking attempts See GSCM STARTING SEQUENCE section 4 5 The max crank max runtime fault LED blinks ra...

Page 7: ... will shut down the generator and indicate a maximum runtime fault by slowly blinking the max crank max runtime LED See GSCM SHUTDOWN CONDITIONS section 6 This runtime fault is only active in the automatic starting mode 6 The GSCM will clear the max runtime fault if the reset terminals 7 8 are momentarily shorted a manual start signal is applied to terminals 5 6 or a period of 12 hours passes from...

Page 8: ...e to 0VDC store setting advance to high Hz position and set to zero volts both must be set 9 To re enable the 5 and 10 minute time delays the GSCM must enter adjustment mode as in paragraph 1 of this section and then the cut in and cut out adjustment re entered and stored without the jumper between terminals 15 and 16 Restoring the GSCM factory default values as described in GSCM Reset Conditions ...

Page 9: ...ad transfer 0 120 Second Load Pre Off Blinking load disconnected cool down period before shutdown Battery Charge Cut In x12 Blinking battery voltage lower than cut in point during 5 minute delay Battery Charge Cut Out x12 Blinking battery voltage greater than cut out point during 10 minute delay 15 75Hz Under Hz Shutdown Blinking generator Hz under speed less than trip point during 10 second delay...

Page 10: ...rank Delay 5 second minimum 60 seconds Maximum crank time Will not energize starter 60 seconds Load transfer delay Ignition and load relays energize together 60 seconds Load pre off delay Ignition and load relays de energize together 120 seconds Battery charge cut in Ignores automatic battery charge function Switched auto start Battery charge cut out Ignores automatic battery charge function Switc...

Page 11: ...e generator has reached 30Hz or half speed If this setting doesn t allow the start input to remain engaged long enough for the generator to stay on line adjust the run disconnect setting to 55Hz See GSCM INITALIZATON AND ADJUSTMENT for changing adjustments The K4 shutdown relay provides a momentary stop signal until the generator AC Hz has dropped to zero The K3 ignition relay provides a continuou...

Page 12: ...rations are shown for both automotive and magneto type with or without fuel valves High speed 3600 RPM generators may need the crank disconnect hertz adjustment set to 20Hz or less to avoid over driving the starter Low Speed Gas Propane Generator with Safeties The low speed gas propane generators also wire the same as in application 2 However the installer should determine ignition type and oil an...

Page 13: ...ession solenoid furnished with the generator must be wired to K4 shutdown relay to energize on shutdown Automatic Generator Powered AC Pump In this application the GSCM is connected to a pressure or level switch into the battery sense terminals To make the appropriate cut in and cut out adjustments See AUTOMATIC STARTING FOR BATTERY CHARGING section 9 The cut in and cut out adjustments must be set...

Page 14: ...a special low voltage generator frequency input version for 12V alternator applications GSCM 12V ALT 255 Hz See AUTOMATIC STARTING FOR BATTERY CHARGING section 9 4 9 Generator Powered Air Conditioner The room thermostat should be line voltage slow action type to minimize short cycling signals the generator to start The GSCM K5 load transfer relay starts the air conditioner after the generator is r...

Page 15: ...ter the GSCM starts the generator with a 3 wire start stop or any other generator starting application to match the type of generator to be controlled If the user desires the voltage from the generator s battery may be connected to the GSCM on terminal 4 and the GSCM will start the generator automatically to charge its own battery when the voltage falls below the battery cut in threshold voltage T...

Page 16: ...m the date of shipment by Atkinson Electronics Inc or its authorized distributors to the original Customer Atkinson Electronics Inc will repair or replace at our option any defective products provided that our inspection discloses that such defects developed under normal and proper use This warranty does not extend to goods subjected to misuse neglect accident or improper installation or to mainte...

Reviews: