ATIM_ACW-MR4_UG_EN_V1.5
b.
ACW-MR4 setup
Emission period and samples in the frame
The transmission period
corresponds to the time interval between each sending of a measurement frame. This
period can be configured from 10 min to 255 h and its default value is 1 hour.
In addition, it is possible to configure the number of samples in a frame
. Thus, several measurements will be carried
out before the sending of the frame which will contain all these measurements.
For example, with a period of 12 minutes and a number of samples of 4, a measurement will be made every 3 minutes
and the 4 samples will be sent in a single frame every 12 minutes.
Finally, it is possible to apply a redundancy of the data
, which means that samples having been sent in the frame
n-1, n-2 or n-3 could be sent again in the frame n to the continuation of the new measurement samples (the most
recent sample first in the frame and the least recent last).
For example, for a history depth of 3, the data of the last 2 frames will be sent, in addition to the new data, in the next
frame.
1
2
3
1
2
3
4
5
6
7
8
9
10
11
12