Single–Point Freeze Protection Heat–Trace Control  

TRACON MODEL FPT 130

Installation and Operation Manual

We manage heat

®

1850 N Sheridan Street

South Bend, Indiana  46628

(574) 233-1202 or (800) 234-4239

FAX (574) 233-2152 or (888) 234-4238

www.networketi.com

Summary of Contents for TRACON FPT 130

Page 1: ...TALTECHNOLOGY INC Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual We manage heat 1850 N Sheridan Street South Bend Indiana 46628 574 233 1202 o...

Page 2: ...he conduit Note Perform the following steps with the circuit breaker to the unit OFF The TRACON FPT 130 is permanently connected equipment and does not have an internal disconnect device When power is...

Page 3: ...to the unit by turning off the circuit breaker protecting the unit Electrical Shock Fire Hazard Any installation involving electric heater wiring must be grounded to earth to protect against shock and...

Page 4: ...tion applications Can use an NEC Class 2 temperature sensor with up to 2 000 ft cable for enhanced installation options Thermistortemperaturesensorwith20ft cableincludedforapplicationsof 40 Fto230 F 4...

Page 5: ...he unit out of direct sunlight Install the FPT on a fixed flat vertical surface using the unit s mounting flanges The mounting flanges accommodate 1 4 or 6 3 mm fasteners The FPT 130 s nonmetallic enc...

Page 6: ...al Manual Load Test To manually energize the load hold Test Reset pushbutton for five seconds The output will switch on and stay on for five minutes or until Test Reset pushbutton is pressed again A m...

Page 7: ...lay contact It is important to make the proper alarm relay connections to achieve the desired result The middle terminal labeled COM Common is used in both wiring configurations Connect one alarm rela...

Page 8: ...3 4 5 6 Temperature Setpoint 1 2 3 4 5 6 50 F 1 2 3 4 5 6 45 F 1 2 3 4 5 6 38 F 1 2 3 4 5 6 30 F Fire Protection Mode 1 2 3 4 5 6 Fire Protection ON 1 2 3 4 5 6 Fire Protection OFF Temperature Sensor...

Page 9: ...en Blinking fast Stuck relay LOW TEMP indicator This blue LED lit solid indicates when the temperature falls more than 2 F 1 C below the setpoint Blinking indicates sensor fault ALARM indicator This r...

Page 10: ...25165 Rev A 6 17 800 234 4239 www networketi com 9 of 13 ENVIRONMENTALTECHNOLOGY INC Model FPT 130 Single Point Freeze Protection Heat Trace Control...

Page 11: ...ge clamp 12 28 AWG leads Alarm relay Terminal Block rising cage clamp 12 28 AWG leads Parameter Settings Temperature setpoints 30 F 38 F 45 F or 50 F 1 1 C 3 3 C 7 2 C or 10 C Low temperature threshol...

Page 12: ...handiseAuthorization clearly on the outside of the shipping container so that it may be correctly processed upon receipt at Environmental Technology For more information about replacement parts or for...