Manual, FT Sensor, Net F/T OEM
Document: 9610-05-1027-05
Pinnacle Park
•
1031 Goodworth Drive
•
Apex, NC 27539 USA
•
Tel: +1.919.772.0115
•
Fax: +1.919.772.8259
Email: [email protected]
12
4.1.3 P603 CAN and DC Power Supply Input Connector
Mating connector housing: Molex 51021-0500
Mating connector contact:
Molex 50058-8000 (28 – 32 AWG)
Molex 50079-8100 (26 – 28 AWG)
Pin
No.
Signal Name
Description
1 DCIN-
DC-supply - input (0VDC)
2 CAN_L
CAN signal -
3 DRAIN
Shield for CAN signal cable
4 CAN_H
CAN
5 DCIN+
DC- input (+11VDC to +24VDC
4.1.4 P604 Transducer Serial Interface Connector
Mating connector housing: Molex 51021-0500
Mating connector contact:
Molex 50058-8000 (28 – 32 AWG)
Molex 50079-8100 (26 – 28 AWG)
Pin
No.
Signal Name
Description
1 POWER_GND
DC Supply 0VDC output
2 RS485-
Serial Interface -
3 ---
reserved
4 RS485+
Serial Int
5 DCIN+
DC output ; 12VDC
4.1.5 P605 Threshold Relay Connector
Mating connector housing: Molex 51021-0600
Mating connector contact:
Molex 50058-8000 (28 – 32 AWG)
Molex 50079-8100 (26 – 28 AWG)
Pin
No.
Signal Name
Description
1 COM_P
Common relay contact, protected
2 NC_P
Normally closed relay contact, protected
1
3 COM
Common relay contact
4 NC
Normally closed relay contact
5 NO_P
Normally open relay contact, protected
1
6 NO
Normally open relay contact
1
Protected means that a resettable fuse is in series to the relay contact and provides protection against over-current. See
section 6.2.2 for more details.